If it is desired to trim the digital level 
value,  he  may  select  a  single  point 
zero  trim  or  a  full  level  trim  that 
requires  the  input  of  both  the  zero 
level  value  and  some  other  level 
value preferably near the end of the 
level measurement tube.
If the transmitter is configured with 
temperature measurement, he 
may select a single temperature 
trim point at 0 deg C or a full 
temperature trim that requires 
trimming both at 0 deg C and 
some other temperature point near 
the upper end of the operating 
temperature range.

Output Current (DAC) Calibration

If the user selects Scaled D/A 
trim from the Calibration screen, 
this screen will appear reminding 
the user that the loop should be 
removed from automatic control 
before proceeding.  When this has 
been done, the user must press 
OK to continue.

The next screen informs the user 
that the rest of the procedure will 
use the values 4.000 to 20.000 in 
the instructions if you are using a 
milliamp meter.  If you are using 
a voltmeter across a resistor, 
select change and provide the 
values that you will be using at the 
current end points.  The user must 
press ENTER when ready.

The HART Communicator now 
instructs the user to connect the 
reference meter that is to be used 
for the current calibration.  The 
user must press OK when ready.

The HART Communicator will now 
command the transmitter to set the 
current output to 4.000mA.  The 
user must press OK when ready 
to have the current output set to 
4.000mA.

When the device has set the 
current output to 4.000mA, the 
user is to enter the reference 
meter reading.  For example, if the 
meter actually reads 4.234mA, that 
value is input with the keypad.  The 
user must press ENTER when the 
current value has been entered.

The transmitter, based on the 
data from the reference meter, 
will calculate a new value for the 
DAC zero calibration constant and 
change the output current based 
on the new constant.  If the current 
read by the reference meter is 
now 4.000mA, the user must press 
ENTER.  If not exact, the user must 
select No and press ENTER to try 
again.

The HART Communicator will now 
command the transmitter to set the 
current output to 20.000mA.  The 
user must press OK when ready 
to have the current output set to 
20.000mA.

When the device has set the 
current output to 20.000mA, the 
user is to enter the reference meter 
reading.  For example, if the meter 
actually reads 19.975mA, that value 
is input with the keypad.  The user 
must press ENTER when ready to 
proceed

The transmitter, based on the 
data from the reference meter, 
will calculate a new value for the 
DAC gain calibration constant and 
change the output current based 
on the new constant.  If the current 
read by the reference meter is now 
20.000mA, the user must press 
ENTER.  If not exact, the user must 
select No and press ENTER to try 
again.

The Current Output calibration 
is now complete.  The HART 
Communicator will now return the 
current output of the transmitter to 
normal operation.

The user is then notified that 
the loop may now be returned 
to automatic control.  After the 
user presses OK the HART 
Communicator returns to the 
Calibration screen.

The HART Communicator is now at 
the starting screen for the Scaled 
D/A trim.

11

Summary of Contents for LTM-300 Series

Page 1: ...81 488 0788 FAX 281 488 7080 EMAIL magtech isemagtech com www isemagtech com LTM 300 Series Magnetostrictive Level Transmitter Instruction Operation Manual 3902 Magnolia Road Pearland Texas 77584 Jan...

Page 2: ...r Installation 3 3 1 Standalone Transmitter Installation 3 3 2 Recommended Wiring Single Loop 4 Section 4 Speci cations Page 4 0 Transmitter Electrical Speci cations 4 4 1 Transmitter Sensor Tube 4 Se...

Page 3: ...hange and continuously activates the sensor in the tube The electronics in the housing process the changing signal and update an analog 4 20 mA output This analog output is precisely proportional to t...

Page 4: ...e base to resolve sub microsecond timing increments The binary number equivalent to the microseconds of the echo travel time is written to an output D A Converter and subsequently converted to a 4 20...

Page 5: ...ectronicshousingmountedatthebottomofthegageforeasyaccess THIS MUST BE SPECIFIED AT TIME OF PURCHASE Installation Note European The cable entry devices and blanking elements of unused apertures shall b...

Page 6: ...gurations A single output version with only one variable that will output a 4 20 mA signal for level The second con guration is a transmitter tted with a second oat to provide a digital output for in...

Page 7: ...elect Data not required Span Trim Move the oat to the 20mA mark 100 on the probe Using the arrow buttons input the correct distance from the zero point and then Select Level O set Enter the desired va...

Page 8: ...ion Problems 6 2 Magnetic Interface 6 3Troubleshooting Power Supply Problems Never move a magnet in a perpendicular motion from along the sensor tube This will always leave a residual eld in the waveg...

Page 9: ...as this could leave magnetic indentation in the sensor wire The LTM 300 level transmitter has an inductor located inside the bulkhead of the sensor tube During operation of the transmitter this induc...

Page 10: ...d the Alarm type In addition this screen presents the procedure to select the Primary variable PV if the transmitter is con gured with both Level and Interface It also displays the menu that will allo...

Page 11: ...t are not normal Any status items not reported are within the normal range of operation or calibration The HART Communicator issues a command to receive the results of the transmitter diagnostics Duri...

Page 12: ...xited if the user selects End The example shows the user selection 4mA The user must press ENTER before the procedure continues When the user selects the Loop test option the HART Communicator display...

Page 13: ...output to 4 000mA the user is to enter the reference meter reading For example if the meter actually reads 4 234mA that value is input with the keypad The user must press ENTER when the current value...

Page 14: ...matic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Zero Level Trim Full Level Trim Starting at...

Page 15: ...now be returned to automatic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Full Level Trim Zero...

Page 16: ...ed Once the measurement is stable the procedure will continue without user intervention The HART communicator will then send the command to the transmitter to calculate the new Temperature zero calibr...

Page 17: ...t Value for 4mA and 20mA by Keypad If you desire to change the Level value at which the Current output is 4mA and 20mA when the Level is the selected Primary Variable or change the Interface value at...

Page 18: ...g the edit box to continue with the reranging of the transmitter On returning to the Keypad rerange screen the values shown for LRV and URV are the changes that the user has made The user should check...

Page 19: ...pper range value getting an update of the digital reading from the transmitter or leaving the 20mA range point as it was If the user accepts the measurement value as the 20mA loop current point the HA...

Page 20: ...h is set in the factory when the unit is prepared for shipment The probe length is used as a reference for a number of diagnostics fuctions as well as setting the URL and LRL shown on the Keypad reran...

Reviews: