Introduction
16
14
15
13
Figure 1-3, Left Side Features
The left side of the MS-PAE Series is equipped with the following features (refer to
fi
gure 1-3):
13
Exhaust Air Vent
- ventilation openings that allows heated air to be removed by the
internal cooling fan.
14
Model/Serial Number Label -
includes model/serial number information, date of
manufacture and inverter and charger speci
fi
cations. See the
MS-PAE Specifi cations
in Appendix A for more information and the different models available.
15
AC Access Cover -
provides access to the internal AC wiring terminal block. This terminal
block is used to hardwire all inverter AC input and output wiring connections. Remove the
two screws to access the AC wiring terminal block.
16
Input circuit breakers -
these circuit breakers protect the unit’s internal wiring and
pass-thru relay on each input (L1 and L2) while in the standby mode. These input circuit
breakers are not branch-circuit rated. These circuit breakers pop out when they open,
press in to reset power capacity.
CAUTION:
Circuit breakers that branch-circuit rated must be installed in the invert-
er’s input and output wiring.
CAUTION:
The inverter’s internal AC transfer relay is rated for 30 amps per leg, the
pass-thru current must be no greater than 30 amps per leg or damage to the relays
may occur.