3.0 Setup
3.2
Remote Menu Items
This section covers the function of each menu item and explains what con-
fi
gurable settings are available from each menu.
3.2.1 AC IN Menu
Use this menu as a quick means of changing your
AC IN
setting to coordinate
with the circuit breaker rating from the incoming AC source.
• AC
IN
– This selection ensures the inverter’s AC loads receive the maxi-
mum current available from the utility or your generator power. Whenever
the utility or generator is connected to the inverter, the current used to
power the AC loads and to charge the batteries is monitored. When the
total current used to power the AC loads and charge the batteries begins
to approach the
AC IN
setting, the current that was used for charging
the batteries will automatically be reduced. This ensures the AC loads
have all the available current when needed. The feature is not available
on MM and MMS Series inverter/chargers.
Default setting:
AC IN = 30 Amps
Range: 5 Amps, 15 Amps, 30 Amps, 50 Amps
Where to set:
Adjust the
AC IN
setting to match the current rating of the
utility power or the generator’s circuit breaker. If using multiple AC sources
(utility and generator) through an AC transfer switch, adjust this setting to
the smaller AC breaker size. This setting is dependent on the stability of the
AC source. If using a generator, factors such as altitude and output voltage
regulation may require a lower setting than the generator’s breaker size. If
the breaker on the AC source is tripping (because it is a weak breaker), try
reducing this setting to the next lower level.
Note:
If the ME-MR is connected to a MSH-RE inverter, the AC IN setting
applies to both inputs (AC1 and AC2).
CAUTION:
The
AC IN
setting does not limit the current to the
inverter loads. If the current to the loads on the output of the in-
verter are greater than the circuit breaker rating on the incoming
AC source, you may experience nuisance tripping of this breaker.
Bottom line shows
current “saved” setting
If this setting is correct,
press
MENU
button to
access different menu items
If a different setting
is required:
press
press
press
To save the current
setting displayed:
ON/OFF
CHANGE
MENU
HOME
SAVE
HOLD
AC IN
30 Amps
AC IN
30 Amps
AC IN
5 Amps
AC IN
15 Amps
AC IN
50 Amps
Figure 3-2, AC IN Selections