13
UNIT CONFIGURATION cont.
SYSTEM CONFIG MENU cont.
Level Measurement cont.
Press ENT to display current
Probe Lo
value. Enter the
exact low level of the process medium. Use proper level
units (inches, centimeters, etc.) previously selected. When
the desired value is displayed, press ENT to store the value.
Supr Password?
will be displayed if the selection is
changed. Enter your
Supr Password
at this time. Press ENT
to accept the password and to display
Probe Hi Point.
Move medium to a high point in the tank or simulate the level
change by moving the probe. Press ENT to display current
Probe Hi
value. Enter the exact level of the process medi-
um. Use proper level units (inches, centimeters, etc.) previ-
ously selected. When the desired value is displayed, press
ENT to store the value.
Supr Password?
will be displayed if
the selection is changed. Enter your
Supr Password
at this
time. Press ENT to accept the password and to display
Previous Menu.
If the application utilizes two probes (dual probe, difference,
or summing) continue to the calibration of
Probe 2
. Press
ENT to display
Probe 2 Select.
Press ENT to display
Level
Units
and begin calibration of Probe 2. Enter all values for
Level Units, Mode Setup, Probe Lo, and Probe Hi points.
System Configuration is now complete. Proceed to I/O
Configuration on Page 20 to continue Unit Configuration.
Probe Lo
Probe Hi