10. Tighten both socket head screws on the clamp to approxi-
mately 35 in./lbs of torque. Slip the Mylar insulator over
the clamp.
11. Screw the transmitter onto the probe until hand tight. The
housing can be wrench-tightened to align the conduit con-
nection with the conduit. Refer to Figure 2 on page 6.
1.5.2.1 Integral Electronics
1. Remove the housing cover. Locate the white wire which is
fastened to the (+) probe terminal. Connect the free end of
this wire to the probe connection screw.
2. Proceed to
Wiring, Section 1.6
.
1.5.2.2 Remote Electronics
1. Connect the positive lead of the interconnection cable
(supplied by MAGNETROL), to the screw terminal at the
top of the probe. Connect the negative lead to the green
ground screw at the base of the housing. Cut the shield;
do not connect it at probe end. Refer to Figure 4 on
page 7.
2. Install the transmitter housing using the bracket (supplied
by MAGNETROL). Make sure to provide adequate clear-
ance to remove the housing cover.
3. Remove the transmitter housing cover. Connect the posi-
tive lead of the interconnection cable to the (+) probe
terminal. Connect the negative lead and shield to the (–)
probe terminal. Refer to Figure 3 on page 6.
4. Proceed to
Wiring, Section 1.6
.