50-613 Kotron
®
Series 82 CE RF Level Transmitter
18
2.4 Agency Approvals
AGENCY
APPROVED MODEL
PROTECTION METHOD
AREA CLASSIFICATION
FM
082-8303-400
Intrinsically Safe
Class
I
, Div 1, Groups A, B, C & D;
082-8303-410
Class
II
, Div 1, Groups E, F & G;
Class
III
, NEMA 4X
Non-Incendive
Class
I
, Div 2, Groups A, B, C & D
Suitable for:
Class
II
, Div 2, Groups F & G;
Class
III
CSA
082-8303-400
Intrinsically Safe
➀
Class
I
, Div 1, Groups A, B, C & D;
082-8303-410
Class
II
, Div 1, Groups E, F & G;
Class
III
, TYPE 4X
Suitable for:
Class
I
, Div 2, Groups A, B, C & D;
Class
II
, Div 2, Groups F & G;
Class
III
082-8303-400
Explosion Proof
➁
Class
I
, Div 1, Groups C & D;
082-8303-410
Class
II
, Div 1, Groups E, F & G
Class
III,
TYPE 4X
5. Non-linear output
a. Incorrect calibration
— Recalibrate unit
b. Excessive loop resistance.
— Reduce loop resistance
c. Damaged jacket on insulated probe
— Replace probe
d. Extreme material build-up on probe
— Possible misapplication; consult factory.
e. Interfering surfaces too close to probe
— Mount probe in better location;
— Use stilling well;
— Use non-metallic brackets and/or standoffs to
position flexible or extremely long rigid probes a
uniform distance from the tank wall.
f. Curved or non-parallel surfaces near probe
— Mount probe in better location;
— Use stilling well.
Loop Resistance vs. Power Supply Voltage
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
0
100
200
300
400
500
600
700
800
900
1000
M
A
X
IM
U
M
L
O
O
P
R
E
S
IS
T
A
N
C
E
(
O
h
m
s
)
(I
n
c
lu
d
in
g
B
a
rr
ie
r
R
e
s
is
ta
n
c
e
)
400 ohms at 24 V
1200 ohms
@ 40 V
Power Supply Voltage (Volts)
1100
1200
1300
➀
Not I.S. (CSA) for Groups E & F when used with a bare probe.
➁
Approval is valid only with the use of insulated probes.