8. Troubleshooting 

8.1 What you should do if...

...there are aluminium components in the system?
For aluminium components in water bearing systems, most manufacturers state a maximum pH value of 8.5. However, it is
known that aluminium components can remain stable at higher pH values, as long as the concentration of the substance s in the
water remain low. If a regulator is installed in a system containing aluminium components, the filling and make-up water of the
system must be prepared using total water demineralisation. However, it may adjust to a pH value of >8.5. With regards to com-
plying with any guarantee claims, we refer to the relevant manufacturer's specifications.

... the system water is still not clear after one year of operating the HWR?
If the throughflow is strongly limited due to individual system parts, causing insufficient circulation, the HWR’s cleaning function
won’t work. All system parts must be fully opened as far as possible. If this is not possible, then all the parts must be rinsed
properly.

...that no water leaks when rinsing the Heating Water Regulator?
If no water is coming out during rinsing, then the lower outlet is blocked. In this case, carefully pierce the opened outlet and loo-
sen the blockage. CAUTION!! Here a large quantity of water may suddenly come out. Set up suitable collection vessels.

...water is leaking from the HWR?
If the water is dripping from the insulation, the automatic quick bleeder is faulty. In this case, it needs to be replaced.

...the water metre is not turning?
Check if the pumps are working and all the valves are open. If the water metre is still not turning, remove both the metre and 
the automatic control valve and clean them. If the water metre is still not working after this, then it needs to be replaced.

...the functional display is still not reacting even though a new anode has been installed?
Test the display using a 1.5V battery. If it does not show any reaction, install a new display. However if it reacts, then there may
not be any water in the device or the anode is not installed properly, possibly there is an oxide layer on the anode. This will need
to be cleaned using a brass wire brush.

...corrosion and silt build-up occur despite HWR use?
Please check if the regulator has been laid out according to our instructions and has been installed correctly so that water
throughflow takes place. Has the maintenance been carried out as described above? Contact us and arrange a water analysis for
troubleshooting.

8.2 Success monitoring

If you would like to check if the HWR plus is really providing corrosion protection,
you can check this by means of certain water parameters. Simply have the heating water
analysed once a year for pH value, conductivity, hardness and dissolved metals. This will provide you with a long-term statistic
and you can determine the corrosion protection function by means of the improved values. The regular water analysis also serves
as a warning system if problems occur.

magnetic

®

...einfach besser

Summary of Contents for HWR 50 plus

Page 1: ...magnetic heating water regulator HWR 50 100 plus Operating manual magnetic einfach besser Anodenstrom...

Page 2: ...heim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade Register HRA 571362 Registered c...

Page 3: ...operating instructions 1 8 Conformity declaration 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator 2 2 Estimating the system volume 2 3 Water content of buffe...

Page 4: ...ring 7 Maintenance 7 1 Functional check flow rate 7 2 Functional check Anode function 7 3 Backwashing desludging container cleaning 7 4 Monitoring water quality 7 5 Anode replacement 8 Troubleshooting...

Page 5: ...l may be used for this purpose This operating manual must always be available at the place of operation 1 2 Area of application The magnetic Heating Water Regulator is used for the electrochemical tre...

Page 6: ...e system from the water pressure or supply network Damaged systems should be decommis sioned immediately Faulty or damaged reaction vessels should only be repaired by specialist personnel authorised b...

Page 7: ...to good engineering practice A leakage and original pressure inspection is carried out 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator The magnetic Heating W...

Page 8: ...mp The advantage is that the treated water ends up directly in other system parts too Due to increasing the return flow temperature it is not suitable for condensing boiler techno logy System group re...

Page 9: ...low before buffer Installation in main return flow before the buffer tanks if oxygenation is likely or circulating impu rities are present Anodenstrom Anodenstrom Anodenstrom Notes on bypass installat...

Page 10: ...al residue Strongly contaminated old systems in particular those which have been pretreated using chemicals must be rinsed completely prior to installing an HWR For this purpose we recommend using our...

Page 11: ...lling water in conjunction with an HWR A residual conductivity of 50 100 S cm must be retained When using a heating water regulator the filling water should not be softened using ion exchange 4 4 Use...

Page 12: ...ntrol and document flow by means of the water metre provided 6 Success monitoring In order to guarantee the successful function of the regulator one should pay particular attention to the following po...

Page 13: ...up however ideally every 2 years checking and documenting water chemistry with regards to pH values and conductivity during maintenance and consulting us if the values strongly deviate from our recom...

Page 14: ...es mA on the display signalises how hard the HWR is working The display allows the following interpretations The display indicator is between 10 and 100 This is the normal operating range The lower th...

Page 15: ...he device After the rinse process close the ball valve 3 and fill the HWR with water 6 After rinsing is concluded lower the magnet on the chain again Open the ball valve 1 on the supply line to the HW...

Page 16: ...e layer is covering the anode which is preventing it from working Clean the anode with a wire brush then it should function again Otherwise check the display func tion using a 1 5V If it doesn t react...

Page 17: ...sulation the automatic quick bleeder is faulty In this case it needs to be replaced the water metre is not turning Check if the pumps are working and all the valves are open If the water metre is stil...

Page 18: ...ductivity upon initial operation Serial number Date Colour of rinsing water Water residue free yes no Metre reading if available Conductivity S cm pH value mA metre Anode replace ment yes no Executor...

Page 19: ...Floor Centre outflow 745 5 895 5 F Depth incl ball valve 460 460 G Minimum distance 1000 1000 Inflow below outflow top 1 1 Performance data System water content 15000 l 35000 l Flow rate max 600l h m...

Page 20: ...term nkheim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade register HRA 571362 Regis...

Reviews: