Magnetic HWR 50 plus Operating Manual Download Page 11

 

magnetic

®

...einfach besser

GDissolved metals

Dissolved metals, such as iron or manganese should not be present in the
water.

Dissolved gases

The content of dissolved gases, such as oxygen and carbon dioxide are
reduced through the use of an HWR. In case of the presence of circulating
bubbles, we recommend installing an additional microbubble deaerator.

TOC (organic carbon)

The TOC content is a measure for the organic contamination of the water. A
value of < 30 mg/l is deemed acceptable. In case of a copper installation, 
the value should not exceed 1.5 mg/l..

Electrical conductivity

When using a Heating Water Regulator, the electrical conductivity of the 
systemwater should be at 50 - 100 μS/cm.

Appearance

The filling water in the heating should be clean and clear.

4.2 Necessity for treating the filling water

In heating systems with oxygen intake due to construction features, one should always endeavour to maintain low electrical
conductivity in the heating water, as this can cut down corrosion processes. As a regulator is mostly used in systems with
high oxygen intake, we recommend a reduction of electrical conductivity to a level of 50-100 μS/cm in conjunction with the
installation. It might be necessary to treat the filling water due to requirements from other component manufacturers, as well 
as if it is necessary to fulfil a directive, such as VDI 2035.

4.3 Type of filling water treatment

If it is necessary to treat the filling water, then one should exclusively use water demineralisation to treat the filling water 
in conjunction with an HWR. A residual conductivity of 50 - 100 μS/cm must be retained. When using a heating water 
regulator, the filling water should not be softened using ion exchange.

4.4 Use of antifreeze agents

No classic antifreeze agents should be used with heating water regulators from magnetic

®

, as these agents often contain

chemical inhibitors. These inhibitors can result in the device breaking down completely. If there is a risk that the pipes in the
heating system could freeze, ethylene glycol that is labelled chemically pure may be used as an antifreeze additive. It should
be noted that the aging of the ethylene glycol leads to the formation of acids which are bound by the HWR. In case of very
high temperatures, the acid formation may exceed the degree of buffering which may result in a temporarily lower pH value. If
you are using antifreeze agents, it is necessary to check the frost protection as well as the pH value of the water annually.

4.5 Influence of electrochemical water treatment on total hardness

In our experience, depending on the composition of the water, the overall hardness of the system water will sink if the pH
value increases, and the related precipitation of calcium carbonate shall decrease slightly.
In low temperature systems, it is possible that existing free carbon dioxide may be bound by the converted magnesium ion to
form magnesium hydrogen carbonate. You don’t need to worry about an uncontrolled increase in hardness, as there will be no 
free carbon dioxide in the heating water over a pH value of 8.2. In contrast to calcium carbonate there is no additional risk of 
damage due to limescale formation due to the good solubility of magnesium carbonate.

Summary of Contents for HWR 50 plus

Page 1: ...magnetic heating water regulator HWR 50 100 plus Operating manual magnetic einfach besser Anodenstrom...

Page 2: ...heim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade Register HRA 571362 Registered c...

Page 3: ...operating instructions 1 8 Conformity declaration 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator 2 2 Estimating the system volume 2 3 Water content of buffe...

Page 4: ...ring 7 Maintenance 7 1 Functional check flow rate 7 2 Functional check Anode function 7 3 Backwashing desludging container cleaning 7 4 Monitoring water quality 7 5 Anode replacement 8 Troubleshooting...

Page 5: ...l may be used for this purpose This operating manual must always be available at the place of operation 1 2 Area of application The magnetic Heating Water Regulator is used for the electrochemical tre...

Page 6: ...e system from the water pressure or supply network Damaged systems should be decommis sioned immediately Faulty or damaged reaction vessels should only be repaired by specialist personnel authorised b...

Page 7: ...to good engineering practice A leakage and original pressure inspection is carried out 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator The magnetic Heating W...

Page 8: ...mp The advantage is that the treated water ends up directly in other system parts too Due to increasing the return flow temperature it is not suitable for condensing boiler techno logy System group re...

Page 9: ...low before buffer Installation in main return flow before the buffer tanks if oxygenation is likely or circulating impu rities are present Anodenstrom Anodenstrom Anodenstrom Notes on bypass installat...

Page 10: ...al residue Strongly contaminated old systems in particular those which have been pretreated using chemicals must be rinsed completely prior to installing an HWR For this purpose we recommend using our...

Page 11: ...lling water in conjunction with an HWR A residual conductivity of 50 100 S cm must be retained When using a heating water regulator the filling water should not be softened using ion exchange 4 4 Use...

Page 12: ...ntrol and document flow by means of the water metre provided 6 Success monitoring In order to guarantee the successful function of the regulator one should pay particular attention to the following po...

Page 13: ...up however ideally every 2 years checking and documenting water chemistry with regards to pH values and conductivity during maintenance and consulting us if the values strongly deviate from our recom...

Page 14: ...es mA on the display signalises how hard the HWR is working The display allows the following interpretations The display indicator is between 10 and 100 This is the normal operating range The lower th...

Page 15: ...he device After the rinse process close the ball valve 3 and fill the HWR with water 6 After rinsing is concluded lower the magnet on the chain again Open the ball valve 1 on the supply line to the HW...

Page 16: ...e layer is covering the anode which is preventing it from working Clean the anode with a wire brush then it should function again Otherwise check the display func tion using a 1 5V If it doesn t react...

Page 17: ...sulation the automatic quick bleeder is faulty In this case it needs to be replaced the water metre is not turning Check if the pumps are working and all the valves are open If the water metre is stil...

Page 18: ...ductivity upon initial operation Serial number Date Colour of rinsing water Water residue free yes no Metre reading if available Conductivity S cm pH value mA metre Anode replace ment yes no Executor...

Page 19: ...Floor Centre outflow 745 5 895 5 F Depth incl ball valve 460 460 G Minimum distance 1000 1000 Inflow below outflow top 1 1 Performance data System water content 15000 l 35000 l Flow rate max 600l h m...

Page 20: ...term nkheim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade register HRA 571362 Regis...

Reviews: