MHR Radio Controller Instruction Manual
June 2017
Page 51 of 58
Alarm
Number
Alarm
Text
Cause of alarm
Effect of alarm
Recovery Action
32
S32. OUT
1 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
33
S33. OUT
2 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
34
S34. OUT
3 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
35
S35. OUT
4 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
36
S36. OUT
5 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
37
S37. OUT
6 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
Summary of Contents for MHR
Page 1: ...MHR Radio Controller June 2017 Part Number 195 50488 0100 R7 2017 Magnetek Material Handling...
Page 21: ...MHR Radio Controller Instruction Manual June 2017 Page 20 of 58...
Page 22: ...MHR Radio Controller Instruction Manual June 2017 Page 21 of 58...
Page 23: ...MHR Radio Controller Instruction Manual June 2017 Page 22 of 58...