background image

-4-

CAUTION: HWG40 and HWG20 heaters with 24
volt electronic ignition come equipped for
installation of an automatic vent damper.
Heaters with 24 volt standing pilot must have
an additional or redundant gas valve installed.
Refer to the appropriate C.G.A. standards and
the instructions supplied with the automatic
vent damper.

1) Observe C.G.A. Standards B149.1 and B149.2

and local safety codes.

2) Ensure that the service switch located on the

motor housing of the automatic vent damper is
at the “AUTOMATIC OPERATION” position.
The “HOLD DAMPER OPEN” position is for
service only.

3) The automatic vent damper must be wired

according to the instructions in section 4.10
ELECTRICAL CONNECTIONS.

Failure to do

so will result in incorrect operation of the
automatic vent damper and a potentially
dangerous condition.

4) Read the manufacturer’s manual provided with

the automatic vent damper and ensure that all
instructions are followed.

4.6 POWER VENTER

The following instructions, and all instructions in
this manual pertaining to power venters, refer to
the Magikist model HWG-PV6B-24 (for the
HWG40) or the HWG-PV4B-24 (for the HWG20)
power venters. Other power venters are neither
approved not tested for use with the HWG40 or
the HWG20 heaters.

1) Observe C.G.A. Standards B149.1 and B149.2

and local safety codes.

2) The power venter must be wired according to

the instructions in the separate document
HWG-PV Power Venter Wiring Instructions.

Failure to do so will result in incorrect
operation of the power venter and a
potentially dangerous condition.

3) Read the manufacturer’s manual provided with

the power venter and ensure that all
instructions are followed.

4.7 FLOW SWITCH

Most heaters are supplied with a flow switch which
you will find installed on the water inlet of the
heater.

Figure 4.7.1

If your heater was supplied without a flow switch,
one 

must 

be installed on the water inlet of the

heater for correct operation of the heater. The flow
switch must be a single pole, single throw,
normally open switch capable of switching a
minimum of 1 amp at 24 VAC. The switch must
also have minimum flow rate of 1.0 U.S. gpm. For
most applications where the high pressure output
of a pump is to be fed directly through the flow
switch into the water inlet of the heater,the
maximum pressure and flow rating of the flow
switch must meet or exceed the operating
pressure and gallons per minute (GPM) of the
pump.

4.8 INLET PLUMBING

When facing the front of the heater, the water inlet
is located on the left, top side. If a flow switch was
provided with your heater, the inlet is 3/8” FNPT
connection. If a flow switch was not provided with
your heater, the inlet is a 3/4” MNPT connection.

In most applications, the
water inlet of the heater
is connected to the high
pressure outlet of a
pump. In such cases,
the direct connection to
the water inlet of the
heater from the pump
must be made with high
pressure hose rated for
the operating pressure
of the pump and the
water outlet temperature
of the heater. Your

heater is normally supplied with a short length of
high pressure hose connected to the water inlet of
the heater that you may use to attach to your inlet
plumbing to. 

Rigid piping must never be

directly connected to the heater due to the
potential damage that may result from pump
vibration being transferred to the heater.

The plumbing to the water inlet of the heater
should be sized for the flow rate desired in order
to prevent pressure loss. There should be no
unnecessary restrictions in the inlet plumbing.
Length should be kept to a minimum as should
the number of elbows and joints. Teflon tape
should be used to seal all joints.

4.9 OUTLET PLUMBING

When facing the front of the heater, the water
outlet is located at the front, slightly to the right of
the center on the HWG40 the HWG20. The water
outlet is a 3/8” FNPT swivel connection.

Figure 4.8.1

WATER

OUTLET

PROSAFE II CONTROL

Flue

Sensor

Temp

Sensor

Flow

Switch

WATER

INLET

PROSAFE II CONTROL

Flue

Sensor

Temp

Sensor

Flow

Switch

FLOW

SWITCH

PROSAFE II CONTROL

Flue

Sensor

Temp

Sensor

Flow

Switch

WATER

OUTLET

PROSAFE II CONTROL

Flue

Sensor

Temp

Sensor

Flow

Switch

WATER

INLET

PROSAFE II CONTROL

Flue

Sensor

Temp

Sensor

Flow

Switch

FLOW

SWITCH

PROSAFE II CONTROL

Flue

Sensor

Temp

Sensor

Flow

Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for HWG20

Page 1: ...DEL HWG40 MODEL HWG20 GAS FIRED COMMERCIAL INDUSTRIAL PRESSURE WASHER HEATERS INSTRUCTION MANUAL V3 02 For heaters equipped with ProSafe II control and 24V electronic ignition HSI or 24V standing pilo...

Page 2: ...this page was intentionally left blank...

Page 3: ...INDICATOR 10 6 4 REQUEST FOR HEAT INDICATOR 10 6 5 PURGE DELAY ON INDICATOR 10 6 6 FLOW ON INDICATOR 10 6 7 THERMOSTAT INDICATOR 10 6 8 EXTERIOR CONTROL INDICATOR 10 6 9 FLUE STATUS INDICATOR 11 6 10...

Page 4: ...this page was intentionally left blank...

Page 5: ...rovide safe and effective control of the heater The PROSAFE II control provides visual status to the operator of the heater through a front panel display on the heater Should some condition arise whic...

Page 6: ...injury Always keep clear of the spray nozzle Do not direct discharge stream at people or electrical apparatus 3 Always keep clear of moving belts and pulleys 4 Never disconnect high pressure hose dur...

Page 7: ...t outage should occur the floor areas should be vented and blown clear before relighting the pilot IMPORTANT Licensed gas installer MUST ensure 3 5 W C for natural gas heaters or 11 W C using an exter...

Page 8: ...w normally open switch capable of switching a minimum of 1 amp at 24 VAC The switch must also have minimum flow rate of 1 0 U S gpm For most applications where the high pressure output of a pump is to...

Page 9: ...uctions later on in this section The second wiring configuration is used when installing the heater without a Magikist control panel If 24VAC is not available you will need to mount the supplied trans...

Page 10: ...tallations that do not utilize a Magikist control panel and another component of your system requires the flow switch for some control aspect the black wire and the EXT FLOW blue wire may be used to d...

Page 11: ...ions on adjusting the flow switch If the DAMPER OPEN indicator does not follow the steps below refer to section 11 0 TROUBLESHOOTING 1 Turn on the high pressure pump or other source supplying water to...

Page 12: ...nob from pilot to on initially due to air inside the gas valve If this occurs repeat the steps in section 5 5 4 If the water inlet of the heater is connected to a high pressure pump start the pump and...

Page 13: ...h affect the operation of the heater are detected and displayed to the operator by the PROSAFE II control Following is a description of the indicators and their function on the PROSAFE II control 6 1...

Page 14: ...flashing slow the PROSAFE II control is indicating a warning that there is water flow through the heater and that it has been continuous for at least 10 minutes This warning is strictly for informatio...

Page 15: ...ose the damper only after there is no water flow for a preset period of time This eliminates the on off cycling a damper experiences in high pressure wash systems where wash guns are opened and closed...

Page 16: ...nt the heater from firing Warning conditions should be attended to promptly in order to ensure the continued safe operation of the heater Should a warning condition arise the indicator light that rela...

Page 17: ...ing another pilot trial period The SmartValve is a continuous retry control Thus it will continuously repeat the pilot trial period followed by the 5 minute delay period until the pilot is successfull...

Page 18: ...burner 9 3 CARE OF MAIN BURNERS Due to condensation from heater coils dripping on the burners a scale build up may occur in the burner jet orifices To remove the burner bar from the heater turn off th...

Page 19: ...an approved coil cleaner may be required See section 8 4 CLEANING HEATER COIL OF SCALE for more information 10 3 FREEZING CONDITIONS Freezing conditions can result in severe damage to the heater coil...

Page 20: ...out frequently standing pilot heaters only Heater is in location that is too drafty Pilot assembly requires service Relocate heater See section 4 1 LOCATION Have gas service personnel check operation...

Page 21: ...ue are at or near freezing Take necessary steps to increase temperature in flue so that coil does not freeze DAMPER OPEN indicator is always on If an automatic vent damper is not installed then this i...

Page 22: ...rature sensor if necessary Temperature setting display flashes E21 and THERMOSTAT indicator is flashing Communicaton problem with temperature sensor short Check connection of temperature sensor to PRO...

Page 23: ...20...

Page 24: ...21...

Page 25: ...SENS TEMP SENS FLOW SW OUTPUT DAMPER brown black 24vac supply black black purple purple blue grey yellow white Refer to manual for wiring of purple blue grey yellow white Duplicate black wires for co...

Page 26: ...SENS FLOW SW OUTPUT DAMPER brown black black black purple purple blue grey yellow Refer to manual for wiring of purple blue grey yellow white Duplicate black wires for convenience Electrical Connecti...

Page 27: ...2 Depth 32 Height without draft hood 46 Height with draft hood 66 3 4 Shipping weight 418 lbs HWG20 Type Instantaneous steel coil Gas supply Natural N models LP P models Coil specifications 3 4 I P S...

Page 28: ...ation any warranties or merchantability or fitness for a particular purpose and all such warranties are hereby disclaimed and excluded by the manufacturer Repair or replacement of defective products a...

Reviews: