Magic-Pak V Series Installation Instructions Manual Download Page 18

Page 18 of 21

507389-01

Issue 1504

replacement, or to access the heat exchanger and flue tube 

extension for cleaning. To remove the combustion inducer:

1.    Remove the control board mounting bracket as described

       previously.

2.    Disconnect the inducer motor leads.

3.    Disconnect the inducer prover switch tubing at the switch.

4.    Disconnect the drain hose tubing at the collector box.

5.     Loosen the hose clamp at the inducer elbow-flue tube joint

        (the upper hose clamp).

6.    Remove the three screws securing the inducer to the cold-

        end header box. Loosen clip at upper mount.

7.    Pull the combustion inducer and elbow away from the vest

       panel to move it free of the mounting legs on the cold-end

       header box, while pulling the inducer elbow free of the flue

       tube extension.

8.    Pull the inducer and elbow out of the compartment.

6.    The flue tube extension can be cleaned if necessary. Leave it

       in place; do not remove it from the unit.

7.    If replacing the inducer with a new part, be sure the correct

       inducer orifice is snapped in place.

8.    For reassembly, follow the above steps in reverse order.

Combustion inducer orifice

The combustion inducer orifice meters the air flow needed for 

proper combustion. Orifices are unique to each heating input, 

and the correct one must always be used. The orifices are color-

coded as an aid. Refer to Table 3:

Refer to Figure 10 to remove the combustion inducer orifice:

1.    The combustion orifice is held in place with snap-fits at the

          inducer inlet and at the indicator tab at the inducer mounting

       foot.

2.    With the combustion inducer out of the unit, carefully pry

        the round portion of the orifice from the inducer inlet.

3.    Remove the indicator tab from the inducer mounting foot.

Model

Orifice color

HWC9N22

Blue

HWC9N33

Black

HWC9N44

Gray

HWC9N55

Brown

Table 3

4.    For reassembly, follow the above steps in reverse order.

Furnace condensate drain

The condensate drain ensures proper evacuation of furnace 

condensate from the collector box and inducer out of the cabinet. 

If hoses are disconnected or if the drain is removed and replaced, 

the drain must be primed as described in the procedure outlined 

in the “Start-up” section. To remove the condensate drain:

1.    Disconnect the upper and lower drain hoses at the condensate

      drain.

2.   Remove the two screws that secure the drain to the vest

       panel.

3.    For reassembly, follow the above steps in reverse order.

4.    Prime the condensate drain as described in the procedure

        outlined in the “Start-up” section.

Heat exchanger inspection

The heat exchanger should be inspected periodically and cleaned 

if necessary. The assembly can be inspected in place, but cleaning 

requires accessing both ends of the primary and secondary tubes, 

which can only be accomplished by removing the heat exchanger 

assembly from the furnace cabinet. To access the primary heat 

exchanger tubes for inspection:

1.    Remove the burner & manifold assembly as described 

        previously.

2.    Remove the control board mounting bracket as described

        previously.

3.    Check the tubes for evidence of soot. If the tubes are clean,

        reassembly is the reverse of the above procedure. If there

          is noticeable soot, continue with the heat exchanger removal

        procedure to remove and clean the heat exchanger.

Combustion

Inducer

Snap into 

place

first (visible 

after

reinstalled 

in unit)

Inducer

Orifice

----Then

Snap into

place

Figure 10

Summary of Contents for V Series

Page 1: ...not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Installati...

Page 2: ...nit must be permanently installed per these installation instructions A room thermostat must control the furnace The use of fixed jumpers that will provide continuous heating is not allowed The return...

Page 3: ...s must be installed in the system and must be maintained during construction Air filters must be replaced upon construction completion The input rate and temperature rise must be set per the furnace r...

Page 4: ...Be certain that the plastic drain tube has free drainage and is not crimped or flattened at any bend Installing Without a Wall Sleeve Refer to the following directions and Figure 1 for guidance in in...

Page 5: ...ent weld piping to street elbow Furnace condensate drain component locations Side exit Condensate Trap Side panel Upper Drain hose From Collector box Lower drain hose To drain fitting reposition and r...

Page 6: ...ecuring the drain fitting to the division panel 3 Remove the drain fitting and rotate it so that it faces the front of the furnace 4 Replace the securing screw 5 Disconnect lower drain hose from drain...

Page 7: ...ps for each appliance connected to the common venting system 7 After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined...

Page 8: ...dition for installations in Canada See rating plate for correct wire ampacity for the cooling chassis required and size wire accordingly The furnace must be isolated from the gas supply piping system...

Page 9: ...sure vary more than 0 3 W C for natural gas or 0 7 W C for propane To adjust the regulator turn the adjusting screw on the regulator clockwise to increase pressure and input or counterclockwise to dec...

Page 10: ...835 34 TAP 4 COOL 208 or 230 800 775 755 735 TAP 5 COOL 208 or 230 880 860 835 815 TAP 1 HEAT 208 or 230 645 59 615 62 590 65 565 N A TAP 2 HEAT 208 or 230 780 49 755 51 730 52 710 54 TAP 3 HEAT 208 o...

Page 11: ...could result in safety shutdown of the burners 1 Adjust to the highest achievable temperature rise within the rise and static pressure ranges specified on the rating plate Depending on specific model...

Page 12: ...nce will try again Blower Control The blower will start approximately 30 seconds after the burners ignite and will stop approximately 120 seconds after the thermostat is satisfied The time delay is pr...

Page 13: ...rnace be inspected annually by a qualified service person Inducer prover switch Ignition Control board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Gas Manifold R...

Page 14: ...efer to Figure 8 Remove the two screws on the burner assembly that secure it to the mounting brackets The mounting brackets contain pins to locate the assembly and hold it in place after the screws ar...

Page 15: ...Page 15 of 21 507389 01 Issue 1504 BURNER MANIFOLD ASSEMBLY REMOVAL Step 7 Mounting Brackets Step 8 Step 9 Step 10 Burner Manifold Assembly Figure 8...

Page 16: ...t without removing any other components To remove the rollout switch 1 Disconnect electrical service and turn off gas to the appliance 2 Disconnect the orange leads at the rollout switch 3 Remove the...

Page 17: ...Page 17 of 21 507389 01 Issue 1504 Ignition board Bracket removal Tabs on Cold End Header box Figure 9 Press down on locking tab then slide bracket Slots on ignition board bracket...

Page 18: ...e unit carefully pry the round portion of the orifice from the inducer inlet 3 Remove the indicator tab from the inducer mounting foot Model Orifice color HWC9N22 Blue HWC9N33 Black HWC9N44 Gray HWC9N...

Page 19: ...assis normally requires no maintenance since it is a closed self contained system System is charged with R410A refrigerant Periodic maintenance is limited to Cleaning the air filter Follow directions...

Page 20: ...Page 20 of 21 507389 01 Issue 1504 Figure 11...

Page 21: ...Page 21 of 21 507389 01 Issue 1504 NOTES...

Reviews: