Magic-Pak HWC8-12 Installation Instructions Manual Download Page 3

Page 3 of 18

507388-01

Issue 1504

The sleeve is not intended as the sole support for the unit.  

An additional support must be provided near the return 

opening  on  the  unit  for  adequate  support.    The  use  of 

vibration isolation material between the unit and the support 

is recommended.

 

 CAUTION

  The return air duct must be provided and sealed to the 

furnace.

  Return air temperature range between 60°F (16°C) and 

80°F (27°C) must be maintained. 

  Air filters must be installed in the system and must be

 

maintained during construction.

  Air filters must be replaced upon construction 

completion.

  The input rate and temperature rise must be set per the 

furnace rating plate.

  One hundred percent (100%) outdoor air must be 

provided for combustion air requirements during 

construction. 

  The furnace heat exchanger, components, duct system, 

air  filters  and  evaporator  coils  must  be  thoroughly 

cleaned following final construction clean-up.

  All furnace operating conditions (including ignition, input 

rate,  temperature  rise  and  venting)  must  be  verified 

according to these installation instructions.

Installing With a Wall Sleeve

Refer to the installation instructions packed with the wall sleeve 

and Figure 1 for guidance in assembly and mounting using a 

wall sleeve.

Make sure the gaskets attached to the sleeve are not damaged.

Summary of Contents for HWC8-12

Page 1: ...not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Installati...

Page 2: ...ion of the unit with clogged or misplaced filters will damage the unit Units may be used for heating of buildings or structures under construction if the following conditions are met The Unit must be...

Page 3: ...d upon construction completion The input rate and temperature rise must be set per the furnace rating plate One hundred percent 100 outdoor air must be provided for combustion air requirements during...

Page 4: ...ing compound The seal must be weathertight to prevent entrance of moisture and water into the building Assure that the unit is completely seated against the gaskets on the wall sleeve Installing Witho...

Page 5: ...ustion inducer The inducer draws the combustion products out of the heat exchanger together with dilution air and forces the mixture from the unit to the outside No special provisions are required for...

Page 6: ...manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1 2 psig or 14 W C If the piping system is to be tested at pressures in excess of 1...

Page 7: ...all sides of the duct are flanged over to permit removal of the cooling chassis if required Use a flexible connection to attach the remainder of the return duct The return duct should be sealed to th...

Page 8: ...55 770 58 735 61 700 64 208 860 52 815 55 770 58 735 61 230 880 51 835 54 790 57 750 60 TAP 1 HEAT 208 or 230 735 49 700 51 670 53 640 56 TAP 2 HEAT 208 or 230 825 43 795 45 770 46 745 48 TAP 3 HEAT 2...

Page 9: ...me additional installation and operating precautions should be taken The following precautions are taken to prevent possible vent system ice blockage that could result in safety shutdown of the burner...

Page 10: ...after the thermostat is satisfied The time delay is preset at the factory and timing can not be adjusted Cooling Sequence of operation When the thermostat system switch is set for COOL the blower wil...

Page 11: ...osen these screws to remove control board mounting bracket Ignition Control board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Primary Limit Mounted to Vest panel...

Page 12: ...wires at the gas valve 7 Refer to Figure 6 Remove the two screws on the burner assembly that secure it to the mounting brackets The mounting brackets contain pins to locate the assembly and hold it in...

Page 13: ...Page 13 of 18 507388 01 Issue 1504 BURNER MANIFOLD ASSEMBLY REMOVAL Step 7 Mounting Brackets Step 8 Step 9 Step 10 Burner Manifold Assembly Figure 6...

Page 14: ...nd slip the rollout switch from beneath the lanced tab on the burner assembly 4 For reassembly follow the above steps in reverse order Flame sensor 1 Remove the control board mounting bracket as descr...

Page 15: ...frigeration system contained in the cooling chassis normally requires no maintenance since it is a closed self contained system System is charged with R410A refrigerant Periodic maintenance is limited...

Page 16: ...Page 16 of 18 507388 01 Issue 1504 Figure 7...

Page 17: ...Page 17 of 18 507388 01 Issue 1504 Figure 8...

Page 18: ...Page 18 of 18 507388 01 Issue 1504 NOTES...

Reviews: