The control board mounting bracket is designed to be removed 

to allow component access for some service procedures.  The 

ignition control board and the inducer prover switch are mounted 

to the bracket.

1. 

Disconnect electrical service and turn off gas to the appliance.

2.  Loosen the two screws securing the control mounting bracket 

(it is not necessary to completely remove them).

3.  Lift the bracket clear of the screws and carefully lower the 

bracket and ignition board to the bottom of the compartment.

4. 

It may be necessary to remove the inducer prover switch 

tubing at the switch.

5.  For reassembly, follow the above steps in reverse order.

Igniter

The igniter can be accessed from the front of the unit without 

removing any other components. To remove the igniter: 

1. 

Disconnect electrical service and turn off gas to the appliance.

2.  Disconnect the orange high voltage spark wire at the ignition 

control board.

3.  Remove the screw and pull the igniter out of the burner 

assembly.

4. 

For reassembly, follow the above steps in reverse order.

Rollout switch

If for any reason the heat exchanger becomes blocked the 

temperature-sensitive rollout switch located beside the burners 

will open and the ignition control will turn off the burners. After 

investigating and correcting the problem, the rollout switch must 

be manually reset by pressing the button on top of it. 

The rollout switch can be accessed from the front of the unit 

without removing any other components. To remove the rollout 

switch: 

1.    Disconnect electrical service and turn off gas to the appliance.

2.   Disconnect the orange leads at the rollout switch.

3.   Remove the screw and slip the rollout switch from beneath

      the lanced tab on the burner assembly.

4.   For reassembly, follow the above steps in reverse order.

Flame sensor

1.    Remove the control board mounting bracket as described

        previously.

2.    Remove the screw and pull the flame sensor from the top

       of burner assembly.

3.    For reassembly, follow the above steps in reverse order.

Primary limit switch

The primary limit will shut down the unit in case of overheating 

and automatically resets when temperature falls  to an acceptable 

level. It is not field adjustable

1.    Remove the control board mounting bracket as described

       previously.

2.    Disconnect the two orange leads at the primary limit switch.

3.    Remove the three screws securing the primary limit switch

        to the vest panel.

4.    For reassembly, follow the above steps in reverse order.

Inducer prover switch

1.   Remove the control board mounting bracket as described

       previously.

2.     Disconnect the two purple leads at the inducer prover switch.

3.    If the tubing is in place, remove it.

4.    Remove the screw securing the switch to the bracket and slip

      the strap end out of the hole in the bracket.

5.    For reassembly, follow the above steps in reverse order.

Burner orifices

Orifices are threaded into the gas manifold. To remove them:

1.    Remove the burner & manifold assembly as described

       previously.

2.   Remove the four screws securing the gas manifold to the

       burner assembly.

3.    Remove the orifices by unscrewing them. Do not use any

        pipe thread sealant during reassembly.

4.    For reassembly, follow the above steps in reverse order.

Combustion inducer

The combustion inducer can be removed for inspection, 

replacement, or to access the heat exchanger and flue tube 

extension for cleaning. To remove the combustion inducer:

1.    Remove the control board mounting bracket as described

       previously.

2.    Disconnect the black inducer motor leads.

Summary of Contents for HWC8-12

Page 1: ...not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Installati...

Page 2: ...ion of the unit with clogged or misplaced filters will damage the unit Units may be used for heating of buildings or structures under construction if the following conditions are met The Unit must be...

Page 3: ...d upon construction completion The input rate and temperature rise must be set per the furnace rating plate One hundred percent 100 outdoor air must be provided for combustion air requirements during...

Page 4: ...ing compound The seal must be weathertight to prevent entrance of moisture and water into the building Assure that the unit is completely seated against the gaskets on the wall sleeve Installing Witho...

Page 5: ...ustion inducer The inducer draws the combustion products out of the heat exchanger together with dilution air and forces the mixture from the unit to the outside No special provisions are required for...

Page 6: ...manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1 2 psig or 14 W C If the piping system is to be tested at pressures in excess of 1...

Page 7: ...all sides of the duct are flanged over to permit removal of the cooling chassis if required Use a flexible connection to attach the remainder of the return duct The return duct should be sealed to th...

Page 8: ...55 770 58 735 61 700 64 208 860 52 815 55 770 58 735 61 230 880 51 835 54 790 57 750 60 TAP 1 HEAT 208 or 230 735 49 700 51 670 53 640 56 TAP 2 HEAT 208 or 230 825 43 795 45 770 46 745 48 TAP 3 HEAT 2...

Page 9: ...me additional installation and operating precautions should be taken The following precautions are taken to prevent possible vent system ice blockage that could result in safety shutdown of the burner...

Page 10: ...after the thermostat is satisfied The time delay is preset at the factory and timing can not be adjusted Cooling Sequence of operation When the thermostat system switch is set for COOL the blower wil...

Page 11: ...osen these screws to remove control board mounting bracket Ignition Control board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Primary Limit Mounted to Vest panel...

Page 12: ...wires at the gas valve 7 Refer to Figure 6 Remove the two screws on the burner assembly that secure it to the mounting brackets The mounting brackets contain pins to locate the assembly and hold it in...

Page 13: ...Page 13 of 18 507388 01 Issue 1504 BURNER MANIFOLD ASSEMBLY REMOVAL Step 7 Mounting Brackets Step 8 Step 9 Step 10 Burner Manifold Assembly Figure 6...

Page 14: ...nd slip the rollout switch from beneath the lanced tab on the burner assembly 4 For reassembly follow the above steps in reverse order Flame sensor 1 Remove the control board mounting bracket as descr...