9
5.
Technical parameter
Model
EM2500
PERFORMANCE CONDITION: Air 27°C/ Water 27°C/ Humid. 80%
Heating capacity (kW)
252.0
COP Range
7.0 - 15.0
PERFORMANCE CONDITION: Air 15°C/ Water 26°C/ Humid. 70%
Heating capacity (kW)
185.0
COP Range
5.5 - 8.0
PERFORMANCE CONDITION: Air 35°C/ Water 28°C/ Humid. 80%
Cooling Capacity (kW)
110.0
TECHNICAL SPECIFICATIONS
Operating air temperature (
℃
)
-15.0 ~ 43.0
℃
Fan direction
Vertical
Power supply
400V/3 Ph/50Hz
Rated input power (kW)
5.7 - 35.8
Rated input current (A)
8.3 - 51.9
Max input current (A)
68
Sound level at 1m dB(A)
58.0 - 72.0
Sound level at 10m dB(A)
38.0 - 52.0
Advised water flux (L/min)
±
20%
1200
Water connection (mm)
110
Net dimension LxWxH (mm)
2601x1051x2069
Net Weight (kg)
1165
Remarks:
This heat pump is able to perform normal within air temp -15
℃
~
43
℃
, efficiency will not be guaranteed out of this
range. Please take into consideration that the pool heater performance and parameters are different under various
conditions.
Related parameters are subject to adjustment periodically for technical improvement without further notice. For details
please refer to nameplate.
Summary of Contents for Elite Max
Page 1: ...1 ...
Page 2: ......
Page 3: ...INDEX ...
Page 6: ...3 Safety Precautions b ...
Page 9: ...6 About your heat pump c ...
Page 13: ...10 6 Dimension A B C D E F G H EM2500 985 1892 1051 1040 2601 525 221 2069 Name Size mm Model ...
Page 14: ...11 Installation Guidance d ...
Page 28: ...25 Operation Guidance e ...
Page 32: ...29 f Testing and Parameters ...
Page 36: ...33 g Commissioning ...
Page 38: ...35 Maintenance h ...
Page 40: ...37 Troubleshooting for common faults i ...
Page 56: ...53 AQ01CKV185 R410A V22 ...