Versión 07/10
6. MOST FREQUENT ERRORS
ERROR
INDICADOR
CAUSA
SOLUCIÓN
1
When the centre is powered
by 230 VAC, any led light up.
Lack of
voltage
Check that voltage reaches the
centre (230 VAC
10%).
2
The right red led flashes
quickly.
(Zoning type installation)
Sensor error
Connect the sound or leave the
resistance which is wired for
default.
3
5 min after switching the
centre on, the zone leds
flashes in all zones and all
grilles are closed.
Incorrect
configuration or
incorret bus
wiring
Check thermostat configuration.
Invert the bus polarity
4
Some of the zone led flashes
and the damper in this zone
is closed.
Bad
communication
The zone is badly configured in the
thermostat SETUP.
Thermostat battery low
5
When the damper should
open
close
(And vice versa).
Motors badly
connected
Check the motor connection.
Polarity (black -, red +)
6
One of the dampers does
not work.
Zone regulator
connection
Check the motor connection.
Polarity (black -, red +)
Check that the regulator is not
obstructed.
7
All of the dampers work
properly but the air
conditioning equipment does
not work.
Air conditioning
equipment badly
connected
Check the Sw1 configuration of the
control centre depending on the
machine type.
Check the equipment connection
to the board.
TECHNICAL CHARACTERISTICS:
Control board
Power: 230 VAC, 50/60 Hz.
Power consumption: 4 VA
2 relay outputs.
Maximum current load: 6 A .Cos
=1
Size (mm): 105 x 90 x 60
Protection level: IP 20
Electric shock insulation Clase II.
Operating temperature: 0 ºC a 55ºC.
Storage temperature:: -10 ºC a 60 ºC.
Thermostat
Power: 2 x 1.5 V LR06 AA batteries (supplied). Average
autonomy 1 year (or more).
Battery wear indicator.
Size (mm) (mm): 112 x 71 x 19.
Operating temperature: 0 ºC a 55ºC.
Storage temperature:: -10 ºC a 60 ºC..
Wall attachment using screws (supplied)
Protection level: IP 20
ECO mode (ordered temp. variation of
3ºC)
Hereby MADEL ATD decalres that the Kca (control board + thermostat) is in compliance with the essential requirements and other
relevant provisions of Directive 1999/5/CE.
http://www.madel.com/esp/pdf/Zoningconformidadkca.pdf
ENGLISH