10
IT
EN
FR
ES
2.0 - CPI SWITCH
2.1 - CPI SWITCH TECHNICAL DATA
• Ambient temperature
: -20 ÷ +60 °C
• Switchable voltage
: max 254 V (dc or ac peak)
• Switchable current
: max 1 A (dc or ac peak)
• Switchable power
: max 40W ohmic
• Resistance
: 200 mΩ
• Protection rating
: IP65
• Protection mode
: II 3G Ex nC IIC T6 Gc X - II 3D Ex tc IIIC T85°C Dc X
• Cable length
: max 5m (3m provided)
2.2 - CPI SWITCH INSTALLATION and CALIBRATION
It is necessary to work in a non-explosive atmosphere and shut off the gas before installation.
• ATTENTION:
The device is supplied with a 3 metre long pre-wired connection cable. This cable
CANNOT
be replaced
with a different one and in the event of damage, the part must be disposed of and replaced with an identical new one; Any
repair (if possible) can only be carried out by the manufacturer;
• In the dangerous zone, wire the ends of the cable with explosion-proof approved equipment (E.g. Terminal box with “E”
protection or increased safety according to EN 60079-7) using the special wire terminals.
• Connect the terminal of the CPI connection cable in series (
5
) to the signalling device;
• Unscrew the cap (
2
) under the valve body (
1
);
• In place of the cap (
2
) screw in the CPI kit (
3
). Make sure that between the body (
1
) and CPI kit (
3
) there is the aluminium
washer (
7
);
• Tighten the CPI kit (
3
) onto the valve body (
1
) with a special commercial spanner;
CPI wiring diagram
open valve / open contact
closed valve / closed contact
SPST