Macurco CX-xx Manual (Rev-1.0) Eng
REV – 1.0
[34-2900-0512-0 ]
33
|
P a g e
6.2
Cleaning
Cleaning of the external surfaces is best carried out using a damp cloth with a mild detergent or soap. Use a vacuum
cleaner with soft brush to remove dust or contamination under the cover. Do not blow out the sensor with
compressed air.
7
Testing
WARNING
Using a certified gas with a concentration other than the one listed for this detector
when conducting a calibration verification test (bump test) will produce inaccurate
readings. This means that higher levels of the gas being monitored may be present and
could result in overexposure. For proper use, see supervisor or User manual, or
contact Technical Support at 1-844-325-3050.
All CX-xx units are factory calibrated and 100% tested for proper operation. During normal operation the green
status indicator LED light will be on steady, the fan & alarm relay will be in standby mode and the 4-20 mA output
will be at 4mA (in clean air). The unit also performs a regular automatic self-test during normal operation. If the unit
detects an improper voltage or inoperable component, it will default into Error mode. In this error mode, the Alarm
relay will be activated, the 4-20 mA current loop will go to 24 mA, the unit will display the error code, the green
status indicator LED light will flash, and the buzzer will chirp intermittently. The Fan relay will also engage if the
Trouble Fan Setting Option is set to “ON”.
7.1
Testing
7.1.1
Operation Test
Check that the green CX-xx status indicator LED light is illuminated continuously. If not, do not proceed with the
tests. If the unit is in error mode, contact your local representative or Macurco technical service representative for
information on resolving the problem.
1.
Remove the single screw in the middle of the front cover of the CX-xx.
2.
Remove the front cover.
3.
Observe the LED light on the front of the CX-xx.
4.
If the light is solid green proceed to step 6.
5.
If the green status indicator LED light is off or flashing, refer to the General section above.
6.
Press
Enter
.
7.
The CX-xx will step through a cycle test:
a.
The display progresses through the bUZ (Buzzer Test) Art (alarm relay test), Frt (fan relay test) then
42t.C and 42t.n (4-20 mA output test). Make sure that the settings are “on” or not disabled “diS”.
Test Description
Test Length Display
bUZ Buzzer Test
3 seconds
Flashes “bUZ”
Art
Alarm Relay Test
5 seconds
Flashes “Art”
Frt
Fan Relay Test
60 seconds Flashes “Frt”
42t.C 4-20 mA Test for CO 130 seconds Flashes “42t.C”
42t.n 4-20mA Test for NO
2
130 seconds Flashed “42t.n”
Summary of Contents for CX-6
Page 43: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 43 P a g e 9 2 Auto Test Menu bUZ...
Page 44: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 44 P a g e 9 3 Configuration Menu CON...
Page 45: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 45 P a g e...
Page 46: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 46 P a g e...
Page 47: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 47 P a g e...
Page 48: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 48 P a g e...
Page 49: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 49 P a g e...
Page 50: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 50 P a g e...
Page 51: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 51 P a g e 9 4 Select Test Menu tst...
Page 52: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 52 P a g e 9 5 CAL Menu...
Page 53: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 53 P a g e...
Page 54: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 54 P a g e 9 6 SEn Menu...