4.
Push
Enter
. The display will show the current setting.
5.
Push
Next
to cycle through the available settings (display will begin flashing).
6.
Push
Enter
to confirm the new setting (display will stop flashing).
7.
Push
Enter
once more to return to the configuration menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
4.5.13
Select Fan Relay Latching Setting – “FrL”
Available options are “On”, “OFF” (default).
To select the Fan Relay Latching Setting, in normal mode:
1.
Push the
Next
button to get to “Con” or the Configuration menu.
2.
Push the
Enter
button to enter the Con menu.
3.
Push
Next
11 times to get to “FrL” or Fan Relay Latching Setting.
4.
Push
Enter
. The display will show the current setting.
5.
Push
Next
to cycle through the available settings (display will begin flashing).
6.
Push
Enter
to confirm the new setting (display will stop flashing).
7.
Push
Enter
once more to return to the configuration menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
4.5.14
Select Trouble Fan Setting – “tFS”
Available options are “On”, “OFF” (default).
To select the Trouble Fan Setting, in normal mode:
1.
Push the
Next
button to get to “Con” or the Configuration menu.
2.
Push the
Enter
button to enter the Con menu.
3.
Push
Next
12 times to get to “tFS” or Trouble Fan Setting.
4.
Push
Enter
. The display will show the current setting.
5.
Push
Next
to cycle through the available settings (display will begin flashing).
6.
Push
Enter
to confirm the new setting (display will stop flashing).
7.
Push
Enter
once more to return to the configuration menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
4.5.15
Select 4-20mA Output Setting – “420”
Available options are “bAS” (default), “EnH”, “OFF”.
NOTE: If the calibration period feature is used and the detector is connected to a panel, the calibration period
information is communicated to the Macurco DVP panel only when “420” is set to “EnH”. Please refer to the
Macurco DVP Panel to confirm if the calibration period feature is supported by the panel. If calibration period
feature is not supported by Macurco DVP panel, ‘bAS’ must be the selected output setting.
To select the 4-20mA Output Setting, in normal mode:
1.
Push the
Next
button to get to “Con” or the Configuration menu.
Summary of Contents for CX-6
Page 43: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 43 P a g e 9 2 Auto Test Menu bUZ...
Page 44: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 44 P a g e 9 3 Configuration Menu CON...
Page 45: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 45 P a g e...
Page 46: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 46 P a g e...
Page 47: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 47 P a g e...
Page 48: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 48 P a g e...
Page 49: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 49 P a g e...
Page 50: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 50 P a g e...
Page 51: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 51 P a g e 9 4 Select Test Menu tst...
Page 52: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 52 P a g e 9 5 CAL Menu...
Page 53: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 53 P a g e...
Page 54: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 54 P a g e 9 6 SEn Menu...