E12
INSTALLATION
Typical Installation
Fig. 1 shows a typical installation.
The installation shown in Fig. 1 is only a guide. The components shown are typical; however, it
is not a complete system design. Contact your distributor for assistance in designing a system
to suit your particular needs.
Pre-Installation Procedure
1. Relieve the pressure.
To reduce the risk of serious injury whenever you are instructed to relieve pressure, always
follow the pressure relief procedure.
2. Close the fluid shut-off valve (Item 4 in Fig.1).
3. Ground the hose and reel or console. Do not use PTFE tape on the pipe joints; it may cause
a loss of ground across the pipe joint.
Installation Procedure
If this is a new installation, or if the oil in the lines is contaminated, flush the lines before you
install the dispense valve.
1: Air inlet
2: Air shut-off valve
3: Oil pump
4: Fluid shut-off valve
5: Meter
6: Hose reel
7: Control valve
NEW INSTALLATION
1. Relieve the pressure.
To reduce the risk of serious injury whenever you are instructed to relieve pressure, always
follow the pressure relief procedure.
2. Close the fluid shut-off valve at each dispense position.
3. Make sure the main fluid outlet valve at the pump is closed, the air pressure to the pump
motor is adjusted, and the air valve is open. Slowly open main fluid valve.
4. Place the hose end (with no dispense valve connected) into a container for waste oil. Secure
the hose in the container so it will not come out during flushing. If you have multiple dispense
positions, first flush the dispense position farthest from the pump, and work your way toward
the pump.
5. Slowly open the shut-off valve at the dispense position. Flush out a sufficient amount of oil to
ensure that the entire system is clean, and close the valve.
6. Repeat step 5 at all other dispense positions.
2
1
3
4
5
6
7
Fig. 1