pompa (P1)
49 MaxCorr.Motore
Massimo valore della corrente di fase
del motore.
Max motor current Maximum rms value of motor phase
current
50 Configur. Relays
Determina la f
unzionalita’ da adibire al
relè. Per
relè d’allarme si intende sia
allarmi di tipo elettrico che idraulico.
Vers.
HC
STD (MM,MT,TT 5.5hp)
:
R1: Alarm (relè d’allarme)
R1: Run (relè di marcia)
R1: Remote Alarm (relè d’allarme su
contro remoto)
R1: Booster (relè comando pompa
booster)
Vers.
HC
ADV (MM,MT,TT 5.5hp)
:
R1:Alm R2:Run (relè allarme, relè
marcia)
R1:Alm R2:RemAlm (relè allarme, relè
allarme su controllo remoto)
R1:A R2:R R3:RA (relè allarme, relè
Marcia, relè Allarme su contr.Remoto)
R1:A R2:R R3:B1 (relè allarme, relè di
marcia, relè booster1)
R1:A R2:B1 R3:B2 (relè Allarme, relè
booster1, relè booster2)
R1:R R2:B1 R3:B2 (relè di marcia, relè
booster1, relè booster2)
R1,R2,R3:Booster (relè booster1,2,3)
Vers.
HC
TT (7.5Hp÷15hp)
:
R1:Alm R2:Alm (Relè allarme)
R1:Run R2:Run (Relè Marcia)
R1:Alm R2:Run (Relè allarme,relè
Marcia)
R1:Alm R2:B1 (Relè allarme,relè
booster1)
R1:Run R2:B1 (Relè Marcia,Relè
booster1)
R1:B1 R2:B2 (Relè Boster 1÷2)
R1:Alm R2:RemAlm (Relè allarme, relè
allarme su controllo remoto)
R1:Run R2:RemAlm (Relè marcia,relè
allarme su controllo remoto)
R1:B1 R2:RemAlm (Relè Booster, relè
allarme su controllo remoto)
Relays Configur.
Determines the function to be
assigned to Relay. The alarm relay
means for both electric and hydraulic
alarms.
Vers.
HC
STD (MM,MT,TT 5.5hp)
:
R1: Alarm (Alarm relay)
R1: Run (Run relay)
R1: Remote Alarm (alarm relay on
remote control)
R1: Booster (booster pump command
relay)
Vers.
HC
ADV (MM,MT,TT 5.5hp)
:
R1:Alm R2:Run (Alarm relay , run
relay)
R1:Alm R2:RemAlm (Alarm relay,
alarm relay on remote control)
R1:A R2:R R3:RA (Alarm, Run,
booster pump command relay, alarm
relay on remote control)
R1:A R2:R R3:B1 (Alarm, Run,
booster pump command relay)
R1:A R2:B1 R3:B2 (Alarm, booster1,
booster2 pump command relay)
R1:R R2:B1 R3:B2 (Run,booster1,
booster2 pump command relay)
R1,R2,R3:Booster (booster1,2,3
pump command relay)
Vers.
HC
TT (7.5Hp÷15hp)
:
R1:Alm R2:Alm (Alarm relay)
R1:Run R2:Run (run relay)
R1:Alm R2:Run (Alarm relay, run
relay)
R1:Alm R2:B1 (Alarm relay,booster1)
R1:Run R2:B1 (run relay,booster1)
R1:B1 R2:B2 (Booster 1÷2)
R1:Alm R2:RemAlm (Alarm relay,
alarm relay on remote control)
R1:Run R2:RemAlm (run relay, alarm
relay on remote control)
R1:B1 R2:RemAlm (Booster, alarm
relay on remote control)
51 Inc Pres Booster
Incremento della pressione impianto
quando il booster è attivo (default
+0.2bar)
Inc Pres Booster
Increase the system pressure when
the booster is on (d0.2 bar)
52 Autoc Tempo Vita
Tempo di utilizzo della autoclave(min,
sec)
Autoc Life Time
Autoclave usage time (min, sec)
53 Autoc Tempo Vita
Tempo di utilizzo della autoclave(gg, h) Autoc Life Time
Autoclave usage time (day, hour)
54 Corr.di picco
Imposta la corrente massima di picco
rilevabile allo spunto, superata la quale
scatta la protezione: "Protetto per I2t".
E’ possibile visualizzare per 5 secondi
la corrente di spunto dalla schermata
principale tenendo premuto il tasto
all’avvio della pompa.
Peak Current
Sets the maximum peak current
detected at start up, after which the
protection snaps: "I2t protected".
The inrush current can be displayed
for 5 seconds from the main menu
pressing
key when the pump
starts.
55 Abilita Remoto
Se ON il drive è in standby e aspetta un
comando esterno per partire
Remote enable
If ON,the inverter is in STANDBY and
wait external command to start (float