CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
Input and Output 1 of this unit are calibrated at the factory
to the default setting (1 – 5V input/4 – 20mA output). You
do not need any calibration unless you need to change these
ranges.
Furthermore, the unit is designed to maintain the described
I/O range setting accuracy (2%: input range setting accura-
cy + output range setting accuracy) even after I/O ranges
have been changed. If these I/O errors need to be compen-
sated, adjust the output as explained in the following.
Output 2 of this unit is calibrated at the factory to meet
the ordered specifications, therefore you usually do not need
any calibration.
For matching both outputs to a receiving instrument or in
case of regular calibration, adjust the output as explained
in the following.
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
5) Go through the same procedure for the output 2.
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.