![background image](http://html2.mh-extra.com/html/m-system/tr30/tr30_instruction-manual_3160454005.webp)
TR30
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8631-A Rev.3 P. 5 / 5
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
50 (1.97)
11
0 (4.33)
6–M3
SCREW
6
(.24)
1
2
3
4
5
6
DIN RAIL
35mm wide
[5 (.20)]
110 (4.33)
98 (3.86)
■
CONNECTION DIAGRAM
In order to improve EMC performance, bond the FE terminal to ground.
Caution: This terminal is NOT a protective conductor terminal.
INTERNAL
POWER
INTERNAL
BUS
INTERNAL
POWER
Ethernet
Configuration
2
3
6
1
SD CARD SLOT
CONNECTOR
RJ-45 CONNECTOR
4
U (+)
V (
–
)
FE
POWER SUPPLY
RUN CONTACT OUTPUT
CONNECTOR
CONNECTOR
WIRING INSTRUCTIONS
■
TORQUE
Wiring screw for separable terminal: 0.5 N·m
Fixing screw for separable terminal: 0.5 N·m
■
SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.25 – 0.75 mm
2
12 max.
6 max.
3 max.
3.2 dia.
■
HOW TO UNMOUNT THE SEPARABLE TERMINAL
The separable terminal of the unit is 2 piece constructions.
It is possible to remove the terminal by loosening two screws
of terminal alternately.