TR30
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8631-A Rev.3 P. 3 / 5
■
STATUS INDICATOR LED
LED
COLOR FUNCTION
PWR
Green
ON when power is on
OFF when power is off
RUN
Green
ON when normal operation
OFF when abnormal operation
TR30
RUN
Green
Blinking while TR30 module is booting up
ON after boot up
OFF when abnormal operation
RECORD Green
ON when logging
OFF when logging stopped
SD CARD Green
ON when SD card recognized
Blinking when accessing to SD card
OFF when SD card is removed or not
recognized
ERROR
Red
Blinking when abnormal operation
OFF when normal operation
■
ETHERNET INDICATOR LED
LED
COLOR
FUNCTION
DPX
Green
ON at full duplex
LNK
Amber
ON at link
■
CONFIGURATION SELECT SW
(*) Factory setting
SW POSITION
CONFIGURATION OBJECT
TR30
TR30 configuraton (*)
I/O
R30 I/O modules configuration
■
DIP SW
(*) Factory setting
• TR30 CONFIGURATION DESTINATION SETTING
SW1
TR30 Configuration USB Destination
OFF
TRGCFG (*)
ON
Terminal for Communication Log
• EVENT REPORTING E-MAIL SETTING
SW2
EVENT REPORTING E-MAIL
OFF
Enable (*)
ON
Disable
• CALENDAR CLOCK BATTERY BACKUP SETTING
SW4
CALENDAR CLOCK BATTERY BACKUP
OFF
Disable (*)
ON
Enable
Note 1: Be sure to set unused SW3 to OFF.
Note 2: In order to prevent battery drain, battery back up is
OFF at factory default. Turn it ON prior to start us-
ing.
■
LOGGING BUTTON
Pressing and holding 1 second starts and stops logging.
■
SD BUTTON
Pressing and holding for 4 seconds turns SD CARD LED off
and makes the card removable.
■
TERMINAL ASSIGNMENT
4
5
NC
FE
6
1
2
U(+)
3
V(-)
NO.
ID
FUNCTION
1
RUN contact output
RUN contact output
2
U (+)
Power supply (24 V DC)
3
V (-)
Power supply (0 V DC)
4
RUN contact output
RUN contact output
5
NC
Not used
6
FE
Functional earth