R7ML-LC2
EM-7805-AX
P. 8 / 10
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
• Discrete Output Unit
Byte
COMMAND (hexadecimal)
RESPONSE (hexadecimal)
REMARKS
5
Discrete output data low 8 bit
Echo back of set value at command area
6
Discrete output data high 8 bit
Echo back of set value at command area
7 – 12
00H
00H
Unused
13
Discrete output data of extension
module low 8 bit
Discrete input data of extension module low 8
bit or echo back of set value at command area
14
Discrete output data of extension
module high 8 bit
Discrete input data of extension module high 8
bit or echo back of set value at command area
"0" for EA8 and EC8x
15 – 31
00H
00H
Unused
• Analog 4-point Input Unit
Byte
COMMAND (hexadecimal)
RESPONSE (hexadecimal)
REMARKS
5
00H
Input 0 low 8 bit
6
00H
Input 0 high 8 bit
7
00H
Input 1 low 8 bit
8
00H
Input 1 high 8 bit
9
00H
Input 2 low 8 bit
10
00H
Input 2 high 8 bit
11
00H
Input 3 low 8 bit
12
00H
Input 3 high 8 bit
13
Discrete output data of extension
module low 8 bit
Discrete input data of extension module low 8
bit or echo back of set value at command area
14
Discrete output data of extension
module high 8 bit
Discrete input data of extension module high 8
bit or echo back of set value at command area
"0" for EA8 and EC8x
15
00H
Status low 8 bit
See I/O data status
16
00H
Status high 8 bit
See I/O data status
17 – 31
00H
00H
Unused
• Analog 2-point Output Unit
Byte
COMMAND (hexadecimal)
RESPONSE (hexadecimal)
REMARKS
5
Output 0 low 8 bit
Echo back of set value at command area
6
Output 0 high 8 bit
Echo back of set value at command area
7
Output 1 low 8 bit
Echo back of set value at command area
8
Output 1 high 8 bit
Echo back of set value at command area
9
– 12
00H
00H
Unused
13
Discrete output data of extension
module low 8 bit
Discrete input data of extension module low 8
bit or echo back of set value at command area
14
Discrete output data of extension
module high 8 bit
Discrete input data of extension module high 8
bit or echo back of set value at command area
"0" for EA8 and EC8x
15 – 31
00H
00H
Unused