R7ML-LC2

EM-7805-AX 

P. 9 / 10

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

• LC2 

Byte

COMMAND (hexadecimal)

RESPONSE (hexadecimal)

REMARKS

5

Input 0 set data low 8 bit

Input 0 low 8 bit or echo back of set value at 
command area

6

Input 0 set data high 8 bit

Input 0 high 8 bit or echo back of set value at 
command area

7

Input 1 set data low 8 bit

Input 1 low 8 bit or echo back of set value at 
command area

8

Input 1 set data high 8 bit

Input 1 high 8 bit or echo back of set value at 
command area

9

Command low 8 bit

Command display low 8 bit or echo back of set 
value at command area

10

Command high 8 bit

Command display high 8 bit or echo back of set 
value at command area

11, 12

00H

00H

Unused

13

Discrete output data of extension 
module low 8 bit 

Discrete input data of extension module  low 8 
bit or echo back of set value at command area

14

Discrete output data of extension 
module high 8 bit 

Discrete input data of extension module  high 8 
bit or echo back of set value at command area

"0" for EA8 and EC8x

15

00H

Status low 8 bit 

See I/O data status

16

00H

Status high 8 bit 

See I/O data status

17 – 31

00H

00H

Unused

I/O DATA DESCRIPTION

 

ANALOG INPUT

0

15

16-bit binary data
Negative values represented in 2

s complements

■ 

ANALOG I/O

 

LC2 COMMAND DETAILS

0

15

■ 

LC2 COMMAND DETAILS

Input 0 Automatic zero correction
Input 0 Zero adjustment
Input 0 Span adjustment
Input 0 Mode setting 
Input 0 Reset offset

Input 1 Automatic zero correction
Input 1 Zero adjustment
Input 1 Span adjustment 
Input 1 Mode setting
Input 1 Reset offset
Input 1 Below range 
Input 1 Within range
Input 1 Over range

Input 0 Below range 
Input 0 Within range
Input 0 Over range

Summary of Contents for R7ML-LC2

Page 1: ...the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ens...

Page 2: ...1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8 9 A B C D E F 4 5 6 7 1 2 3 10 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 MECHATROLINK Setting Rotary SW MECHATROLINK Connector Station Address Setting Rotary SW Statu...

Page 3: ...1 7 SW1 4 SW1 5 SW1 6 SW1 7 Averaging OFF OFF OFF OFF 2 samples ON OFF OFF OFF 4 samples OFF ON OFF OFF 8 samples ON ON OFF OFF 16 samples OFF OFF ON OFF 32 samples ON OFF ON OFF 64 samples OFF ON ON...

Page 4: ...V 3 FG SLD0 INPUT 0 EXCITATION 0 V0 C0 C1 V1 Strain Gauge INPUT 0 OUTPUT 0 SLD1 INPUT 1 EXCITATION 1 INPUT 1 OUTPUT 1 MECHATROLINK CONNECTOR MECHATROLINK CONNECTOR MECHATROLINK connectors are internal...

Page 5: ...nating resistors Consult the instruction manual for the Master SRD SRD SLD SRD SRD SLD Slave SRD SRD SLD SRD SRD SLD Slave SRD SRD SLD MECHATROLINK Cable MECHATROLINK Cable MECHATROLINK COMMUNICATION...

Page 6: ...H 00H 3 17 bytes at 17 bytes mode CDRW 03H Command Data Format Data transmission command is located in upper layer of Application Layer Command Byte COMMAND hexadecimal RESPONSE hexadecimal REMARKS 0...

Page 7: ...es 8 15 00H ID Product information data 16 31 00H 00H Unused CONNECT 0EH Command Data Format Starts communication with the master Byte COMMAND hexadecimal RESPONSE hexadecimal REMARKS 5 VER VER MODE S...

Page 8: ...11 00H Input 3 low 8 bit 12 00H Input 3 high 8 bit 13 Discrete output data of extension module low 8 bit Discrete input data of extension module low 8 bit or echo back of set value at command area 14...

Page 9: ...Unused 13 Discrete output data of extension module low 8 bit Discrete input data of extension module low 8 bit or echo back of set value at command area 14 Discrete output data of extension module hi...

Page 10: ...the actual load to the sensor 2 Set 2000 decimal to Input set data area 3 Set 1 to Span adjustment bit When the adjustment is completed LED2 for Input 0 or LED10 for Input 1 turns on 4 After checking...