background image

R7M-RR8

P. 2 / 4

EM-7803-T Rev.1

 

I / O STATUS INDICATOR LED

Output and feedback input status are indicated with LED.

ON: LED on
OFF: LED off

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

 

4

DA

5

6

7

1

2

3

DG U(+) V(–)

DB

SLD

FG

(1)  DB 

(2)  SLD  Shield
(3)  FG 

FG

(4)  DA 

(5)  DG 

(6)  U(+)  Power input
(7)  V(–)  Power input

OUTPUT TERMINAL ASSIGNMENT

10

NC

11

Y0

12

Y1

1

NC

2

C0

3

C1

13

Y2

4

C2

14

Y3

5

C3

15

Y4

6

C4

16

Y5

7

C5

17

Y6

8

C6

9

C7

18

Y7

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

NC

No connection

10

NC

No connection

2

C0

Common 

11

Y0

Output 0

3

C1

Common 

12

Y1

Output 1

4

C2

Common 

13

Y2

Output 2

5

C3

Common

14

Y3

Output 3

6

C4

Common

15

Y4

Output 4

7

C5

Common 

16

Y5

Output 5

8

C6

Common 

17

Y6

Output 6

9

C7

Common 

18

Y7

Output 7

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and
OFF to invalidate.
(Factory setting OFF)

 

EXTENSION MODULE

Combinations with all extension modules are available.

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 

normally.

RUN

Red

Turns on when the refresh data is received 

normally.

ERR

Red

Turns on when the received data is abnormal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The
left switch determines the tenths place digit, while the right 
switch does the ones place digit of the address.

 

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Node Address Setting (x10)

BAUD RATE

Baud Rate is selected with the rotary switch.

 

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0: 38.4 kbps
1: 19.2 kbps
2: 9600 bps
3: 4800 bps
4: 2400 bps

5: 1200 bps
6: 14.4 kbps
7: 28.8 kbps
8: 57.6 kbps
9: 115.2 kbps

OPERATING MODE

Extension (SW1-1, 1-2)

SW1-1

SW1-2

EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input 8 or 16 points

OFF

ON

Discrete output 8 or 16 points

(*) Factory setting
Note : Be sure to set unused SW1-3 through 1-8 to OFF.

 

PC CONFIGURATOR

The following parameters can be set with using PC Configu-
rator Software.

• Modbus parameters: Parity, bit length, stop bit

COMPONENT IDENTIFICATION

■ 

SIDE VIEW

■ 

FRONT VIEW

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

1 2 3 4 5 6 7 8

0 1 2 3 4 5 6 7

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED 
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  I/O Status Indicator LED
(G)  Modbus, Power Supply Terminals
(H)  Output Terminals
( I )  Terminating Resistor SW

(A)

(G)

(H)

(B)

(C)

(D)

(E)

(F)

0 1 2 3 4 5 6 7

CNFG.

INPUT

OUTPUT

(I)Terminating Resistor SW

TERM

ON

OFF

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG