R7G4FML3-6-DA16

P. 7 / 10

EM-7774-A Rev.2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

• 

CONNECT (0EH) 

Starts communication with master station.

BYTE

COMMAND

RESPONSE

REMARKS

0

CONNECT (0EH)

CONNECT (0EH)

Establish connection command

1

00H

00H

Not used

2

CMD_CTRL

CMD_STAT

Refer to CMD_CTRL/CMD_STAT.

3
4

30H

30H

MECHATROLINK application layer: 30H

5

00H

00H

Communication mode: Asynchronous, single transmis

-

sion, subcommand disabled

6

COM_TIME

COM_TIME

Communication cycle: Multiple of transmission cycle. 

E.g. Transmission cycle: 0.5 msec, communication cycle: 2 

msec. Set 4 (=2/0.5)

7

30H or 01H

30H or 01H

Profile type  30H: Standard I/O  01H: Event-driven

≥ 8

00H

00H

Reserve

• 

DISCONNECT (0FH) 

Stops communication with master station.

BYTE

COMMAND

RESPONSE

REMARKS

0

DISCONNECT (0FH)

DISCONNECT (0FH)

Release Connection command

≥ 1

00H

00H

Reserve

• 

DATA_RWA (20H) 

Transmits I/O data to master station. Data allocation is following. 

Data size is 16 bytes.

BYTE

COMMAND

RESPONSE

REMARKS

0

DATA_RWA (20H)

DATA_RWA (20H)

Transmmit I/O data

1

00H

00H

Not used

2

CMD_CTRL

CMD_STAT

Refer to CMD_CTRL/CMD_STAT.

3
4

CH0 OUT LO

CH0 IN LO

CH x OUT:   Output data

 

(Refer to “ Output Data ” 

 

 under Input / Output Data Details)

CHx IN:  Input data

 

 (Refer to “ Input Data ” 

 

  under Input /Output Data Details)

5

CH0 OUT HI

CH0 IN HI

6

CH1 OUT LO

CH1 IN LO

7

CH1 OUT HI

CH1 IN HI

8

CH2 OUT LO

CH2 IN LO

9

CH2 OUT HI

CH2 IN HI

10

CH3 OUT LO

CH3 IN LO

11

CH3 OUT HI

CH3 IN HI

12

00H

00H

Not used

13

00H

00H

Not used

14

00H

00H

Not used

15

00H

00H

Not used

Summary of Contents for R7G4FML3-6-DA16

Page 1: ...ffect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure CE conformity This unit is suitable for Pollution Degree 2 Altitude up to 2000 meters The power supply and the external power supply must satisfy SELV requirements in accordance with the cur...

Page 2: ...actory setting 03H Station Address Setting x1 Station Address Setting x10 01 2 3 4 5 6 7 8 9 A B C D EF 01 2 3 4 5 6 7 8 9 A B C D EF PC CONFIGURATOR JACK The PC Configurator is used to set the following parameters for each channel Read rate setting Choose among 1 msec 5msec 10msec 20msec 50msec 70msec 100msec 200msec For more information about the programming using the R7CFG please refer to the R...

Page 3: ...3 Remove the upper hook of the unit from the DIN rail 1 2 3 SURFACE MOUNTING 1 Insert the two DIN rail mounter sliders until it clicks once as shown below 1 1 2 Mount the unit with M4 screws referring the External Dimensions Torque 1 4 N m DIN RAIL MOUNTING RIGHT ANGLE Mounting 1 Insert the longer DIN rail mounter slider until it clicks twice as shown below 1 2 Set the upper hook at the rear side ...

Page 4: ... 3 dia 4 deep 2 17 dia 0 16 deep 130 5 12 140 5 51 154 6 06 CONNECTION DIAGRAM Connect the unit as in the diagram below Note In order to improve EMC performance bond the FE terminal to ground Caution FE terminal is NOT a protective conductor terminal 1 5 10 2 6 4 7 13 8 9 14 12 15 11 16 17 18 3 6 7 24V DC 0V MECHATROLINK CONNECTOR 3 FE MECHATROLINK CONNECTOR INPUT CONNECTION EXAMPLES COM COM X2 X4...

Page 5: ...NICATION Transmission cycle 125 µsec 250 µsec 500 µsec 1 64 msec with 1 msec increments Communication cycle 125 µsec through 64 msec Applicable profile Standard I O profile cyclic communication Event driven communication acquiring ID profile event driven communication Data size 16 bytes Station address 03H through EFH set with rotary switches Cyclic communication Available Event driven communicati...

Page 6: ...ONFIG 04H Setup device command 1 00H 00H Not used 2 CMD_CTRL CMD_STAT Refer to CMD_CTRL CMD_STAT 3 4 00H 00H Recalculation of parameters and set up Other than 00H is not supported 5 00H 00H Reserve ALM_RD 05H Reads alarm or warning BYTE COMMAND RESPONSE REMARKS 0 ALM_RD 05H ALM_RD 05H Read alarm or warning command 1 00H 00H Not used 2 CMD_CTRL CMD_STAT Refer to CMD_CTRL CMD_STAT 3 4 0000H 0000H Re...

Page 7: ...pe 30H Standard I O 01H Event driven 8 00H 00H Reserve DISCONNECT 0FH Stops communication with master station BYTE COMMAND RESPONSE REMARKS 0 DISCONNECT 0FH DISCONNECT 0FH Release Connection command 1 00H 00H Reserve DATA_RWA 20H Transmits I O data to master station Data allocation is following Data size is 16 bytes BYTE COMMAND RESPONSE REMARKS 0 DATA_RWA 20H DATA_RWA 20H Transmmit I O data 1 00H...

Page 8: ...H2 OUT HI CH2 Data High order 8 bits Not in use CH3 OUT LO CH3 Data Low order 8 bits Not in use CH3 OUT HI CH3 Data High order 8 bits Not in use CMD_CTRL CMD_CTRL command area is following BIT FUNCTION REMARKS 0 2 Reserve Not used 3 ALM_CLR 0 Clear alarm warning disabled 1 Clear alarm warning triggered 4 5 Reserve Not used 6 7 CMD_ID Not used in the standard I O command profile 8 15 Reserve Not us...

Page 9: ...30D4 125 µsec 17 Max Transmission Cycle 4 Yes 0x0061A800 64 msec 18 Increments of Transmission Cycle 4 Yes 0x00000001 Available to 31 25 62 5 125 250 500 µsec 1 64 msec 1 msec increments 19 Min Communication Cycle 4 Yes 0x000030D4 125 µsec 1A Max Communication Cycle 4 Yes 0x0061A800 64 msec 1B Transmission Bytes 4 Yes 0x00000002 16 Bytes 1C Transmission Bytes Current Setting 4 Yes 0x00000002 16 By...

Page 10: ...Rev 2 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail info m system co jp I O DATA DESCRIPTION 0 15 0 OFF 1 ON Input 0 Input 1 Input 2 Input 3 Input 15 Input 7 Input 8 DISCRETE INPUT ...

Reviews: