![M-system R7G4FML3-6-DA16 Instruction Manual Download Page 6](http://html1.mh-extra.com/html/m-system/r7g4fml3-6-da16/r7g4fml3-6-da16_instruction-manual_3220346006.webp)
R7G4FML3-6-DA16
P. 6 / 10
EM-7774-A Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
•
ID_RD (03H)
Reads the product ID.
BYTE
COMMAND
RESPONSE
REMARKS
0
ID_RD (03H)
ID_RD (03H)
Read ID command
1
00H
00H
Not used
2
CMD_CTRL
CMD_STAT
Refer to CMD_CTRL/CMD_STAT.
3
4
ID_CODE
ID_CODE
Refer to ID_CODE
5
OFFSET
OFFSET
OFFSET: designates the place to read data
6
SIZE
SIZE
SIZE: specify the size of data to read
7
≥ 8
00H
ID
Product's ID
•
CONFIG (04H)
No parameter to set for this unit. Immediately response with completion.
BYTE
COMMAND
RESPONSE
REMARKS
0
CONFIG (04H)
CONFIG (04H)
Setup device command
1
00H
00H
Not used
2
CMD_CTRL
CMD_STAT
Refer to CMD_CTRL/CMD_STAT.
3
4
00H
00H
Recalculation of parameters and set up. Other than 00H
is not supported.
≥ 5
00H
00H
Reserve
•
ALM_RD (05H)
Reads alarm or warning
BYTE
COMMAND
RESPONSE
REMARKS
0
ALM_RD (05H)
ALM_RD (05H)
Read alarm or warning command
1
00H
00H
Not used
2
CMD_CTRL
CMD_STAT
Refer to CMD_CTRL/CMD_STAT.
3
4
0000H
0000H
Read current alarm or warning.
12 points max. (2 bytes in 8th to 31st byte)
Other than 00H is not available.
5
6
0000H
0000H
0
7
≥ 8
00H
00H
0
•
ALM_CLR (06H)
Clears alarm or warning
BYTE
COMMAND
RESPONSE
REMARKS
0
ALM_CLR (06H)
ALM_CLR (06H)
Clear alarm or warning command
1
00H
00H
Not used
2
CMD_CTRL
CMD_STAT
Refer to CMD_CTRL/CMD_STAT.
3
4
0000H
0000H
Clear current alarm or warning. Other than 00H is not
available.
5
≥ 6
00H
00H
Reserve