INPUT RANGE

• 

Wide span

:  -10 – +10V DC, -5 – +5V DC, 0 – 10V DC,  

 

0 – 5V DC, 1 – 5V DC

• 

Narrow span

: -1 – +1V DC, 0 – 1V DC, -0.5 – +0.5V DC

• 

Current input

:  -20 – +20mA DC, 0 – 20mA DC, 

 

4 – 20mA DC

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

PC CONFIGURATOR

The following parameter items can be set with using PC Configurator Software (model: R7CON).
Refer to the users manual for the R7CON for detailed operation of the software program.

 

INTERFACE SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

Communication Timeout

0.0 – 3276.7 (sec.)

1.0 (sec.) 

Status Data

ON: Disable
OFF: Enable

OFF: Enable

Serial ID

English one-byte characters within 8 characters

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Input Range

-10 to +10 V DC
-5 to +5 V DC
-1 to +1 V DC
0 to 10 V DC
0 to 5 V DC
1 to 5 V DC
0 to 1 V DC
-0.5 to +0.5 V DC
-20 to +20 mA DC 
0 to 20 mA DC 
4 to 20 mA DC

-10 to +10 V DC

Zero scale

-32000 to +32000

0

Full scale

-32000 to +32000

10000

Bias

-320.00 to +320.00

0.00

Gain

-3.2000 to +3.2000

1.0000

 

EXTENSION MODULE SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Output Hold/Clear

Output Hold
Output Clear

Output Hold

Summary of Contents for R7D-SV4

Page 1: ...nt is suitable for use in Installation Catego ry II and in a Pollution Degree 2 environment Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipment is...

Page 2: ...in the baud rate setting detected at the startup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 through 9 it analyzes the PLC s network to determine the b...

Page 3: ...detailed operation of the software program INTERFACE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Communication Timeout 0 0 3276 7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID...

Page 4: ...5 5 22 DIN RAIL 35mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 18 M3 SCREW TERMINALS for INPUT 6 24 TERMINAL BLOCK for DeviceNet POWER CONNECTION DIAGRAM 1 VH0 10 VL0 11 I0 2 COM0 INPUT 0 3 VH1 12...

Page 5: ...e R7D EA16 with Status Analog Input Module CH0 CH1 CH2 CH3 Begin 0 1 2 3 Output Data Analog Input Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Inp...

Page 6: ...ster Master to R7D R7D SV4 4 0 EXTENSION MODULE Transmitted data word for the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D ECx 0 1 STATUS Stat...

Page 7: ...ng the R7D Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out o...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Page 9: ...ment Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions fr...

Page 10: ...ween cables and noise sources Grounding in pig tail form is not effective Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external...

Reviews: