R7D-SV4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7802-A  Rev.7  P. 2 / 10

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

MS

X10

X1

NODE ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

NS

2 3 4

1

5

(A)  Status Indicator LED
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  DeviceNet, Power Supply Terminals
(G)  Input Terminals

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

STATE

TO INDICATE

MS

Green

Operating in a normal condition

Blinking Green Standby (needs commissioning)

Red

Critical failure

Blinking Red

Minor failure

OFF

No power supplied

NS

Green

Link on-line and connections in the 
established state

Blinking Green Link on-line but no connections in 

the established state

Red

Critical link failure

Blinking Red

Minor link failure

OFF

No power supplied

 

NODE ADDRESS

Node Address is selected between 1 and 63 in decimal.  The 
left switch determines the tenth place digit, while the right 
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 125 kbps (factory setting)
1 : 250 kbps
2 : 500 kbps
3 thr. 9 : Auto-tracking

The R7D communicates in the baud rate setting detected at 
the startup with the switch set to the positions 0 (125 kbps), 
1 (250 kbps) or 2 (500 kbps).
For the settings 3 through 9, it analyzes the PLC’ s network 
to determine the baud rate on the network.

 

OPERATING MODE

(*) Factory setting

• Extension: SW1-1, 1-2

SW1-1

SW1-2

EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

• Conversion Rate / Accuracy: SW1-3, 1-4

SW1-3

SW1-4

CONVERSION RATE / ACCURACY

OFF

OFF

80 msec. / ±0.1% (*)

ON

OFF

40 msec. / ±0.2%

OFF

ON

20 msec. / ±0.4%

ON

ON

10 msec. / ±0.8%

• Input Range: SW1-5, 1-6, 1-7, 1-8

SW1-5

SW1-6

SW1-7

SW1-8

INPUT RANGE

OFF

OFF

OFF

OFF

-10 – +10V DC (*)

ON

OFF

OFF

OFF

-5 – +5V DC

OFF

ON

OFF

OFF

-1 – +1V DC

ON

ON

OFF

OFF

0 – 10V DC

OFF

OFF

ON

OFF

0 – 5V DC

ON

OFF

ON

OFF

1 – 5V DC

OFF

ON

ON

OFF

0 – 1V DC

ON

ON

ON

OFF

-0.5 – +0.5V DC

ON

OFF

OFF

ON

-20 – +20mA DC

OFF

ON

OFF

ON

4 – 20mA DC

ON

ON

OFF

ON

0 – 20mA DC

ON

ON

ON

ON

PC Configurator setting

 

DeviceNet TERMINAL ASSIGNMENT

2

3

4

1

5

NO.

ID

FUNCTION, NOTES

1

V+

Network power

2

CAN_H

Network data High

3

Drain

Shield

4

CAN_L

Network data Low

5

V–

Network power supply –

 

INPUT TERMINAL ASSIGNMENT

10

VL0

11

I0

12

VL1

1

VH0

2

COM0

3

VH1

13

I1

4

COM1

14

NC

5

NC

15

VL2

6

VH2

16

I2

7

COM2

17

VL3

8

VH3

9

COM3

18

I3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

VH0 Wide span volt. 0 10

VL0 Narrow span volt. 0

2 COM0 Common 0

11

I0

Current range 0

3

VH1 Wide span volt. 1 12

VL1 Narrow span volt. 1

4 COM1 Common 1

13

I1

Current range 1

5

NC

No connection

14

NC

No connection

6

VH2 Wide span volt. 2 15

VL2 Narrow span volt. 2

7 COM2 Common 2

16

I2

Current range 2

8

VH3 Wide span volt. 3 17

VL3 Narrow span volt. 3

9 COM3 Common 3

18

I3

Current range 3

Summary of Contents for R7D-SV4

Page 1: ...nt is suitable for use in Installation Catego ry II and in a Pollution Degree 2 environment Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipment is...

Page 2: ...in the baud rate setting detected at the startup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 through 9 it analyzes the PLC s network to determine the b...

Page 3: ...detailed operation of the software program INTERFACE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Communication Timeout 0 0 3276 7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID...

Page 4: ...5 5 22 DIN RAIL 35mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 18 M3 SCREW TERMINALS for INPUT 6 24 TERMINAL BLOCK for DeviceNet POWER CONNECTION DIAGRAM 1 VH0 10 VL0 11 I0 2 COM0 INPUT 0 3 VH1 12...

Page 5: ...e R7D EA16 with Status Analog Input Module CH0 CH1 CH2 CH3 Begin 0 1 2 3 Output Data Analog Input Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Inp...

Page 6: ...ster Master to R7D R7D SV4 4 0 EXTENSION MODULE Transmitted data word for the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D ECx 0 1 STATUS Stat...

Page 7: ...ng the R7D Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out o...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Page 9: ...ment Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions fr...

Page 10: ...ween cables and noise sources Grounding in pig tail form is not effective Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external...

Reviews: