EM-7802-A  Rev.7  P. 4 / 10

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

2 3 4

1

5

30 (1.18)

[5 (.20)]

3 (.12)

3 (.12)

5.5 (.22)

DIN RAIL

35mm wide

54 (2.13)

17 (.66)

50 (1.97)

18.5 (.73)

115 (4.53)

18–M3 SCREW 

TERMINALS

for INPUT

6 (.24)

TERMINAL BLOCK for

DeviceNet, POWER

 

CONNECTION DIAGRAM

1

VH0

10

VL0

11

I0

2

COM0

INPUT 0

3

VH1

12

VL1

13

I1

4

COM1

INPUT 1

6

VH2

15

VL2

16

I2

7

COM2

INPUT 2

8

VH3

17

VL3

18

I3

9

COM3

INPUT 3

■ 

Input Connection Examples

VHn

VLn

In

+

– COMn

WIDE SPAN

VOLTAGE

VHn

VLn

In

+

– COMn

NARROW SPAN

VOLTAGE

VHn

VLn

In

+

– COMn

Be sure to close across VLn and In terminals for a current input.

CURRENT

RANGE

CAN_L

V–

Drain

CAN_H

V+

EXTENSION CONNECTOR

Summary of Contents for R7D-SV4

Page 1: ...nt is suitable for use in Installation Catego ry II and in a Pollution Degree 2 environment Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipment is...

Page 2: ...in the baud rate setting detected at the startup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 through 9 it analyzes the PLC s network to determine the b...

Page 3: ...detailed operation of the software program INTERFACE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Communication Timeout 0 0 3276 7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID...

Page 4: ...5 5 22 DIN RAIL 35mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 18 M3 SCREW TERMINALS for INPUT 6 24 TERMINAL BLOCK for DeviceNet POWER CONNECTION DIAGRAM 1 VH0 10 VL0 11 I0 2 COM0 INPUT 0 3 VH1 12...

Page 5: ...e R7D EA16 with Status Analog Input Module CH0 CH1 CH2 CH3 Begin 0 1 2 3 Output Data Analog Input Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Inp...

Page 6: ...ster Master to R7D R7D SV4 4 0 EXTENSION MODULE Transmitted data word for the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D ECx 0 1 STATUS Stat...

Page 7: ...ng the R7D Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out o...

Page 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Page 9: ...ment Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions fr...

Page 10: ...ween cables and noise sources Grounding in pig tail form is not effective Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external...