R7C-TS4

EM-7801-B  Rev.10  P. 6 / 10

MG CO., LTD. www.mgco.jp

5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

I/O DATA DESCRIPTIONS

0

15

16-bit binary data
Negative values represented in 2

s complements

■ 

ANALOG INPUT

0

15

Input 0  (Output 0)
Input 1  (Output 1)
Input 2  (Output 2)      8 points

Input 15  (Output 15)

Input 3  (Output 3)
     :              :                                 16 points
Input 7  (Output 7)
Input 8  (Output 8)
     :              :

0 : OFF  
1 : ON 

■ 

DISCRETE I/O

0

15

Input 0 (Burnout, input range error)
Input 1 (Burnout, input range error)
Input 2 (Burnout, input range error)

Unused

Input 3 (Burnout, input range error)
Input 0 (ADC error)
Input 1 (ADC error)
Input 2 (ADC error)
Input 3 (ADC error)

     :

Unused

Burnout, input range error (≤ -15%, ≥ +115%)
     0 : Normal     1 : Error
ADC error (no response from ADC)
     0 : Normal     1 : Error

■ 

STATUS

Analog input module without extension module can show input status of each channel.

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

Summary of Contents for R7C-TS4

Page 1: ...be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of th...

Page 2: ...switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Di...

Page 3: ...o noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting...

Page 4: ...4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 Input Connection Example INn INn CJn CJn T C CJC SENSOR EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG...

Page 5: ...ocated other than at the extreme ends of communication line DATA ALLOCATION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused RWwn 0 1 2 3 Interval t...

Page 6: ...Burnout input range error Unused Input 3 Burnout input range error Input 0 ADC error Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Burnout input range error 15 115 0 Normal 1 Error ADC...

Page 7: ...dequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choos...

Page 8: ...tically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impe...

Page 9: ...y be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise ove...

Page 10: ...nts of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cov...

Reviews: