R7C-TS4

EM-7801-B  Rev.10  P. 5 / 10

MG CO., LTD. www.mgco.jp

5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

COMMUNICATION CABLE CONNECTIONS

DA
DB

DG

SLD

FG

Master Unit

DA
DB

DG

SLD

FG

Remote Unit

DA
DB

DG

SLD

FG

Remote Unit

TERMINATOR

TERMINATOR

blue

white

yellow

Be sure to connect the terminating resistor included in the product package to the unit at both ends of communication line.
The terminator must be connected across DA and DB.
The Master Unit can be located other than at the extreme ends of communication line.

DATA ALLOCATION

Analog input 0

Analog input 1

Analog input 2

Analog input 3

RWrn+0

+1

+2

+3

Unused

Unused

Unused

Unused

RWwn+0

+1

+2

+3

Interval-timed Response (X)

Refresh Data (Y)

RX(n+0)F to RX(n+0)0

Reserved

(Status)

RX(n+0)F to RX(n+0)0

Reserved

(Status)

Unused

RX(n+0)F to RX(n+0)0

Reserved

(R7C-EA16)

Unused

0

F

1F

Interval-timed Response (X)

0

F

1F

Refresh Data (Y)

• Without Extension Module

0

F

1F

Interval-timed Response (X)

0

F

1F

Refresh Data (Y)

• With Extension Module R7C-EA16

RY(n+0)F to RY(n+0)0

Unused

(R7C-EC16x)

0

F

1F

Interval-timed Response (X)

0

F

1F

Refresh Data (Y)

• With Extension Module R7C-EC16x

   

ANALOG INPUT

Summary of Contents for R7C-TS4

Page 1: ...be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of th...

Page 2: ...switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Di...

Page 3: ...o noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting...

Page 4: ...4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 Input Connection Example INn INn CJn CJn T C CJC SENSOR EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG...

Page 5: ...ocated other than at the extreme ends of communication line DATA ALLOCATION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused RWwn 0 1 2 3 Interval t...

Page 6: ...Burnout input range error Unused Input 3 Burnout input range error Input 0 ADC error Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Burnout input range error 15 115 0 Normal 1 Error ADC...

Page 7: ...dequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choos...

Page 8: ...tically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impe...

Page 9: ...y be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise ove...

Page 10: ...nts of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cov...