WARNINGS AND CAUTIONS WHEN LAYING CABLES

Signal cables connected to the R7C contain high-frequency components.  Since these cables has the same effect as an antenna, 
they emit these high-frequency components to the external space as noise or overlaps noise from the external space on them-
selves.
Cables with shielding should be used for the signal line due to the above reason.
EMC conformance test is conducted in the condition that shielded cables and earth clamps are used with the R7C.
Warning and cautions when laying cables are stated below.  These points of cautions are illustrated in the next page.

• Use shielded cables for those signal cables installed out of the control panel and for thermocouple and RTD extension wires.
• All the network cables connected to R7C should be shielded.
• Use exclusively designed cables for the CC-Link.
• Expose the shield at a part of the cable cover, clip it with an earth clamp, and ground it to the internal panel of the control 

panel.  A drain wire connected to the panel in a pig-tail form cannot maintain low impedance against high-frequency noise, 
thus grounding (noise shielding) in this form will not be effective.

Supplement: 

Additional measures may be taken depending upon actual installation sites.  These points of cautions are illustrated in the 
next page.

• Keep cables as short as possible.  It prevents noise emissions from the cables and noise overlapping to the cables.
• Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise.  Ferrite core can be attached close 

to the cable outlet of the control panel or close to the I/O terminal or connector, whichever is more effective.  Also, the impact 
might be reduced by winding the cable around the ferrite core for extra turns or attaching multiple ferrite cores.

• Keep cables which are easily affected by noise away from those which can be a noise source.

Motor Drive

Cable

Power Supply 

Cable

DC Signal Cable

Network Cable

Analog Signal

Cable

Often being a noise source

Often subject to noise interference.

In the following are examples of effective ways to lay cables separately: 

• Keeping physical distance (farther than 20 cm from motor drive cables, farther than 10 cm for other groups).
• Dividing off by a grounded metal plate
• Grouping into separate grounded metal pipes or cable shields.

Wires on each side of a filter should not be too close to each other.  Noise could ride onto the other side of cable.
Extra attention needs to be paid at the following parts.

• Noise filter that is enclosed in power cables.
• Ferrite core that is attached to signal cables.
• Noise limiting circuit (surge quenching circuit, transient absorber circuit, etc.) that is enclosed in signal cables.

Summary of Contents for R7C-TS4

Page 1: ...be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of th...

Page 2: ...switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Di...

Page 3: ...o noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting...

Page 4: ...4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 Input Connection Example INn INn CJn CJn T C CJC SENSOR EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG...

Page 5: ...ocated other than at the extreme ends of communication line DATA ALLOCATION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused RWwn 0 1 2 3 Interval t...

Page 6: ...Burnout input range error Unused Input 3 Burnout input range error Input 0 ADC error Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Burnout input range error 15 115 0 Normal 1 Error ADC...

Page 7: ...dequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choos...

Page 8: ...tically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impe...

Page 9: ...y be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise ove...

Page 10: ...nts of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cov...

Reviews: