R7C-RR4
P. / 4
EM-780-AC
■
OUTPUT TERMINAL ASSIGNMENT
10
5
6
1
2
7
8
9
3
4
Y3
C3
NC
NC
C0
Y0
Y1
Y2
C1
C2
■
POWER SUPPLY, CC-LINK TERMINAL ASSIGNMENT
4
DA
5
6
7
1
2
3
DG
U(+)
V(–)
DB
SLD
FG
(1) DB
(2) SLD
(3) FG
(4) DA
(5) DG
(6) U(+)
(7) V(–)
White
Shield
FG
Blue
Yellow
Power input (24V DC)
Power input (0V)
NO.
ID
FUNCTION
NO.
ID
FUNCTION
1
NC No connection
6
NC No connection
2
C0
Common 0
7
Y0
Output 0
3
C1
Common 1
8
Y1
Output 1
4
C2
Common 2
9
Y2
Output 2
5
C3
Common 3
10
Y3
Output 3
INDICATOR LED
■
STATUS INDICATOR LED
PWR
RUN
ERR
SD
RD
STATUS
ON
ON
BL
BL
ON
Communicates normally with occasional CRC errors due to noise interface.
ON
ON
BL
BL
ON
Communicates normally but the Baud Rate and/or Station Address switches failed.
ERR LED blinks approximately in 0.5 second intervals.
ON
ON
BL
BL
OFF
----
ON
ON
BL
OFF
ON
CRC error found in the received data. Unable to respond.
ON
ON
BL
OFF
OFF
----
ON
ON
OFF
BL
ON
Normal communication
ON
ON
OFF
BL
OFF
----
ON
ON
OFF
OFF
ON
Unable to receive data addressed to the station.
ON
ON
OFF
OFF
OFF
----
ON
OFF
BL
BL
ON
Performs the interval-timed responses but CRC error found in receiving the refresh data.
ON
OFF
BL
BL
OFF
----
ON
OFF
BL
OFF
ON
CRC error found in the data addressed to the station.
ON
OFF
BL
OFF
OFF
----
ON
OFF
OFF
BL
ON
Link is not started.
ON
OFF
OFF
BL
OFF
----
ON
OFF
OFF
OFF
ON
No data addressed to the station. Or unable to receive data addressed to the station due to
noise interface. (Missing parts of the data sent from the master)
ON
OFF
OFF
OFF
OFF
Unable to receive data due to wire breakdown
ON
OFF
ON
OFF
ON/OFF Faulty Baud Rate and/or Station Address setting
OFF
OFF
OFF
OFF
OFF
Power input removed. Or power supply failure.
OFF = OFF, ON = ON, BL = Blinking
---- = Inconceivable in normal operations (e.g. LED failure)
■
BAUD RATE
Baud Rate is selected with the rotary switch.
■
TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate. (Factory setting OFF)
■
INDICATOR LED
Feedback input status and output bit status are indicated
with LED.
ON: LED on
OFF: LED off
5
4
3
2 1 0 9
8
7
6
Baud Rate Setting
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps