R7C-RR4
P. / 4
EM-780-AC
DATA ALLOCATION
0
15
Feedback input 0
Feedback input 1
Feedback input 2
Feedback input 3
Not Used
Output 3 OFF
0: OFF 1: ON
Output 0 ON
Output 0 OFF
OUTPUT SETTING
Each output is set with 2 bits. Refer to the table below for
output setting.
NO.
BIT
SETTING
FUNCTION
Output 0
8, 9
0, 0
No operation
1, 0
Output 0 ON
0, 1
Output 0 OFF
1, 1
Invalid
Output 1
10, 11
0, 0
No operation
1, 0
Output 1 ON
0, 1
Output 1 OFF
1, 1
Invalid
Output 2
12, 13
0, 0
No operation
1, 0
Output 2 ON
0, 1
Output 2 OFF
1, 1
Invalid
Output 3
14, 15
0, 0
No operation
1, 0
Output 3 ON
0, 1
Output 3 OFF
1, 1
Invalid
Do not set both bits 1. If the 2 bits are simultaneously 1,
the module will not operate normally.
For repeating the output of ON pulse, after setting (0, 0),
set (1, 0) once again.