background image

R7C-RR4

P. 4 / 4

EM-780-AC

CONNECTION DIAGRAM

Connect the unit as in the diagram below.

7

10

2

5

7

9

2

4

3

10

5

Y0

Y1

C1

Y2

C2

Y3

C3

C0

8

Y0

Blue

Remote Control

Transformer

White

C3

C0

Y3

Red

Remote Control

Relay

Blue

Remote Control

Relay

4

1

2

5

3

DA

DB

DG

SLD

FG

6

7

U(+)

V(–)

� 

Output Connection Example

Red

Blue

WIRING INSTRUCTIONS

 SOLDERLESS TERMINAL  mm (inch)

Refer  to  the  drawing  below  for  recommended  ring  tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  Applicable 
wire size: 0.3 – 0.75 mm

2

3.2 (.13) dia.

4 min.

(.16)

12 (.47) max.

6 max. (.24)

3 (.12) max.

EXTERNAL DIMENSIONS

  unit: mm (inch)

2

3

4

1

5

10

7

8

9

6

4

5

6

7

1

2

3

30 (1.18)

[5 (.20)]

3 (.12)

5.5 (.22)

7–M3 SCREW

TERMINALS

for CC-Link, POWER

10–M3 SCREW 

TERMINALS

for OUTPUT

DIN RAIL

35mm wide

54 (2.13)

17 (.66)

6 (.24)

50 (1.97)

6 (.24)

18.5 (.73)

115 (4.53)

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such 
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive 
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this 
warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original 
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED 
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR 
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

Summary of Contents for R7C-RR4

Page 1: ... the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14...

Page 2: ... to receive data addressed to the station ON ON OFF OFF OFF ON OFF BL BL ON Performs the interval timed responses but CRC error found in receiving the refresh data ON OFF BL BL OFF ON OFF BL OFF ON CRC error found in the data addressed to the station ON OFF BL OFF OFF ON OFF OFF BL ON Link is not started ON OFF OFF BL OFF ON OFF OFF OFF ON No data addressed to the station Or unable to receive data...

Page 3: ...CTION Output 0 8 9 0 0 No operation 1 0 Output 0 ON 0 1 Output 0 OFF 1 1 Invalid Output 1 10 11 0 0 No operation 1 0 Output 1 ON 0 1 Output 1 OFF 1 1 Invalid Output 2 12 13 0 0 No operation 1 0 Output 2 ON 0 1 Output 2 OFF 1 1 Invalid Output 3 14 15 0 0 No operation 1 0 Output 3 ON 0 1 Output 3 OFF 1 1 Invalid Do not set both bits 1 If the 2 bits are simultaneously 1 the module will not operate no...

Page 4: ...anufactures to be free from defects in materials and workmanship during the 36 month period following the date that such product was originally purchased if such product has been used under normal operating conditions and properly maintained M System s sole liability and purchaser s exclusive remedies under this warranty are at M System s option the repair replacement or refund of the purchase pri...

Reviews: