TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

94 (3.70)

5.9 (.23)

102 (4.02)

5

6

7

8

1

2

3

4

8–M3

EURO TERMINAL

WIRE INSERTION ANGLE: approx. 7°

 

CONNECTION DIAGRAM

BUS CONNECTOR

INTERNAL

POWER 

INTERNAL

BUS

INPUT 1

INPUT 2

6

7

2

3

+

T/C

comp. leadwire

+

+

T/C

comp. leadwire

+

• Unused Input Channels

Close across the unused input terminals as shown below.  
(Choose K (CA) thermocouple for unused channels.)

2

3

INPUT 1

6

7

INPUT 2

Short

If unused input terminals are not short-circuited, status in-
dicator LED blinks in red (0.5 sec. cycle), and a burnout flag 
is set in the PLC or the host device.

 

WIRING INSTRUCTIONS

• Applicable wire size

    Solid:    

0.2 to 2.5 mm

2

 (0.55 to 1.75 dia.)

    Stranded:   0.2 to 2.5 mm

2

 (Tinning wire ends may cause 

contact failure and therefore is not recom-
mended.)

    Ferruled:  0.2 to 1.5 mm

2

 (0.55 to 1.35 dia.)

• Expose wire conductors by 8 mm (0.31”).

8 mm

8 mm

3.7 mm dia.

max.

3.7 mm dia.

max.

Wire exposure

Recommended
ferruled wire