background image

R6D-TS2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7781-BG  Rev.3  P. 4 / 4

• How to Connect Wires

Screwdriver

Wire

Insert a wire.  Confirm that the wire tip hits the bottom and 
tighten the screw with a screwdriver.
Confirm that the wire’s insulation tube is not caught in the 
terminal. (Torque: 0.3 N

.

m)

Screwdriver

Wire

8 mm

6 mm

PC CONFIGURATOR

With configurator software, settings shown below are avail-
able.
Refer to the software manual of R6CON for detailed opera-
tion.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Sensor type 

K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
(PR)

K (CA)

Lower range value 

Depends on sensor type 0.00 (degC)

Upper range value 

Depends on sensor type 0.00 (degC)

Fine zero adjustment  -320.00 to +320.00 (%)

0.00 (%)

Fine gain adjustment  -3.2000 to +3.2000

1.0000

Scaled range Zero 

-32000 to +32000

0

Scaled range Span 

-32000 to +32000

10000

Burnout 

Upscale, Downscale

Upscale

 

CHANNEL BATCH SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Loss of internal bus 
communication detec-
tion time 

0.0 – 99.9 (sec.)

1.0 (sec.)

Conversion rate

250, 500 (msec.)

500 (msec.)

Temperature unit 

degC, degF, K

degC

CJC 

ON, OFF

ON

Limit 

-15 to +115%
Scaled range Zero / Span

-15 to +115%