R5CON USERS MANUAL  EM-9272 Rev.10

4. NETWORK MODULE

4.1 ETHERNET SETTINGS

With the Ethernet Interface Module (model: R5-NE1) connected, click <Ethernet Settings> button.

<Upload> button 

Reading the current setting from the R5 module and showing on the window.

<Download> button  Writing the setting on the current display to the R5 module.
<Exit> button  

Close the window.

Item

Function

Selectable Range

(must be used within this range)

IP Address

Enter IP Address

0 to 255 (integer)

Subnet Mask

Enter Subnet Mask

0 to 255 (integer)

MAC Address

Shows MAC Address

TCP Socket

Enter TCP Socket Port No. to each port (1 thr. 4)
Modbus/TCP port number is 502.

502

Linger

Enter time to close TCP Socket. (factory set to 1800)
TCP Socket closed after no communication (Set 1800 for 180.0 sec.) for 
the preset time.
This function is selectable with the R5-NE1 Ver 0.04 or higher.  
‘CNG’ is indicated on the screen when the version is lower than 0.04.

0 to 32767 (integer)

CAUTION !

Ethernet settings, once set, are enabled only after the power supply to the R5 network module is turned off and on.

4.2 COMMUNICATION TIMEOUT

Timeout means the time interval for the network module to recognize 
interrupt communication when the network module terminates commu-
nication with the host PLC or PC, or the latter interrupt communication 
with the former.

(1)Enter a value between 0 and 32767.  In order to set to 30 seconds, 

enter 300. (Factory setting = 3 seconds)

(2)Click [Download].

Summary of Contents for R5 Series

Page 1: ...ries Remote I O R5X PC CONFIGURATOR Model R5CON Users Manual http www m system co jp 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Tel 81 6 6659 8201 Fax 81 6 6659 8510 E mail info m system c...

Page 2: ...6 2 3 CONNECTING DISCONNECTING THE COMMUNICATION LINE 8 3 VIEWS FUNCTIONS PARTICULAR TO MODULES 9 3 1 ANALOG I O MODULE 9 3 2 THERMOCOUPLE RTD INPUT MODULE 10 3 3 CT PT AC CURRENT VOLTAGE INPUT MODUL...

Page 3: ...respectively are sent to the host PLC or PC FILE MANAGING The parameter configuration for each module can be saved as a file on the PC Therefore you can configure a set of param eters without actually...

Page 4: ...program or Program and feature Property dialog box of Programs and feature appears on the display 3 Choose R5CON among the list of installed applications 4 Choose Add Remove 5 Remove Programs From You...

Page 5: ...I O module 2 1 STARTING QUITTING THE R5CON Display images shown in this manual may change in detail when the software version is updated STARTING THE R5CON Press Start on the task bar and choose R5CON...

Page 6: ...cation line CONTROL PANEL Card No list Shows the selectable card numbers Click the arrow at the right to choose a card number in order to switch the main frame from Overview to the detail view for the...

Page 7: ...version Input Type Type of thermocouple and RTD Type I O Card Module Type None No card mounted Model No One of the Model No mounted Ch 1 Value Ch 2 Value Analog I O value for Ch 1 Analog I O value fo...

Page 8: ...up on the screen Confirm that the power is supplied to the R5 modules and that the configurator jack of the R5 network module and the COM port of the PC is firmly connected with the attached cable Ch...

Page 9: ...d No Shows Slot No Card Type Shows I O module hardware type Version No Shows firmware version No Zero Scale Enter 0 scaling value 32000 to 32000 Full Scale Enter 100 scaling value 32000 to 32000 Bias...

Page 10: ...Span Adj Enter fine 100 adjustment value gain 3 2000 to 3 2000 Zero Base Enter 0 temperature factory setting 0 As shown on the display Full Base Enter 100 temperature factory setting 0 As shown on th...

Page 11: ...No Shows Slot No Card Type Shows I O module hardware type Version No Shows firmware version No Zero Scale Enter 0 scaling value 32000 to 32000 Full Scale Enter 100 scaling value 32000 to 32000 Bias Ze...

Page 12: ...ws I O module hardware type Version No Shows I O module s firmware version No DI Data Shows current input data status 3 5 DISCRETE OUTPUT MODULE Item Function Card No Shows Slot No Card Type Shows I O...

Page 13: ...Download button Downloading the setting on the current display to the R5 module Item Function Selectable Range must be used within this range Card No Shows Slot No Card Type Shows I O module hardware...

Page 14: ...TCP port number is 502 502 Linger Enter time to close TCP Socket factory set to 1800 TCP Socket closed after no communication Set 1800 for 180 0 sec for the preset time This function is selectable wi...

Page 15: ...Save on the menu bar 3 Specify a location and a file name to save 5 2 READING PARAMETERS Click Open in the pulled down menu The PC Program reads the saved parameters but are not downloaded automatica...

Reviews: