R5CON USERS MANUAL EM-9272 Rev.10
4. NETWORK MODULE
4.1 ETHERNET SETTINGS
With the Ethernet Interface Module (model: R5-NE1) connected, click <Ethernet Settings> button.
<Upload> button
Reading the current setting from the R5 module and showing on the window.
<Download> button Writing the setting on the current display to the R5 module.
<Exit> button
Close the window.
Item
Function
Selectable Range
(must be used within this range)
IP Address
Enter IP Address
0 to 255 (integer)
Subnet Mask
Enter Subnet Mask
0 to 255 (integer)
MAC Address
Shows MAC Address
TCP Socket
Enter TCP Socket Port No. to each port (1 thr. 4)
Modbus/TCP port number is 502.
502
Linger
Enter time to close TCP Socket. (factory set to 1800)
TCP Socket closed after no communication (Set 1800 for 180.0 sec.) for
the preset time.
This function is selectable with the R5-NE1 Ver 0.04 or higher.
‘CNG’ is indicated on the screen when the version is lower than 0.04.
0 to 32767 (integer)
CAUTION !
Ethernet settings, once set, are enabled only after the power supply to the R5 network module is turned off and on.
4.2 COMMUNICATION TIMEOUT
Timeout means the time interval for the network module to recognize
interrupt communication when the network module terminates commu-
nication with the host PLC or PC, or the latter interrupt communication
with the former.
(1)Enter a value between 0 and 32767. In order to set to 30 seconds,
enter 300. (Factory setting = 3 seconds)
(2)Click [Download].