R5CON USERS MANUAL EM-9272 Rev.10
3.2 THERMOCOUPLE & RTD INPUT MODULE
<Upload> button
Uploading the current setting for the I/O module to the window.
<Download> button Downloading the setting on the current display to the R5 module.
Item
Function
Selectable Range
(must be used within this range)
Card No.
Shows Slot No.
Card Type
Shows I/O module hardware type
Version No.
Shows firmware version No.
Input Type
Shows T/C or RTD input type setting
Burnout
Shows the burnout type setting
Zero Scale
Enter 0% scaling value
-32000 to 32000
Full Scale
Enter 100% scaling value
-32000 to 32000
Bias [Zero Adj.]
Enter fine 0% adjustment value (bias)
-320.00 to 320.00
Gain [Span Adj.]
Enter fine 100% adjustment value (gain)
-3.2000 to 3.2000
Zero Base
Enter 0% temperature. (factory setting = 0)
As shown on the display
Full Base
Enter 100% temperature. (factory setting = 0)
As shown on the display
Value
Shows the current uploaded temperature value.
Limit
(R5-TS V1.00 or higher)
Check the box to limit the input range within Zero Scale and Full Scale
when scaling is set. When no scaling is set and/or when the check box is
not selected, the input range is limited within -15 to +115%.
CAUTION !
Scaling is disabled when both Zero Scale is set to ‘0’ and Full Scale is set to ‘10000.’ The input module will send multiplied
raw data: with °C temperature unit, raw data is multiplied by 10 (e.g. 25.5°C is converted into 255), and with °F temperature
unit, the integer section of raw data is directly converted into the data (e.g. 135.4°F is converted into 135).