I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■
16-BIT ANALOG DATA (models: R5-SV, YV, DS, YS, RS, TS, etc.)
0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
With °C or Kelvin temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Negative values are represented in 2’s complements.
0
15
■
4-POINT DISCRETE DATA (models: R5-DA4, DC4, etc.)
0
15
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 4 (Output 4)
Not Used (Remains “0”)
0 : OFF
1 : ON
■
16-POINT DISCRETE DATA (models: R5-DA16, DC16, etc.)
0
15
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 4 (Output 4)
Input 16 (Output 16)
0 : OFF
1 : ON