background image

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

90 (3.54)

5.6

(.22)

90 (3.54)

LOCKING CLAMP

POSITIONING GUIDE

18 (.71)

 

CONNECTION DIAGRAM

Note:  In order to improve EMC performance, bond the FG 

terminal to ground.

Caution:  FG terminal is NOT a protective conductor terminal.

INTERNAL POWER

INTERNAL BUS

CONFIGURATION JACK

JACK

BUS CONNECTOR

DA
DB

DG

SLD

FG

To Other

Modbus

Devices

Note: The FG terminal is not connected with the FG of the power supply 
          module (model: R5-PS).

WIRING INSTRUCTIONS

 

EURO TYPE CONNECTOR TERMINAL (Modbus)

Applicable wire size: 0.2 to 2.5 mm

2

 (AWG24 to 12)

Stripped length: 7 mm

COMMUNICATION CABLE CONNECTIONS

TERMINATOR

Tx+ / Rx+
Tx– / Rx–

SG

Rx+
Rx–

HOST PC

DA
DB

DG

SLD

FG

DA
DB

DG

SLD

FG

MODBUS

INTERFACE

MODULE

MODBUS

INTERFACE

MODULE

FG

FG

R5-NM1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-6104  Rev.8  P. 3 / 7

Summary of Contents for R5-NM1

Page 1: ...nit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 30 to 90 RH i...

Page 2: ...MODE RTU Binary ASCII 8 OFF ON 1 Bit assignment according to Parity and Data Mode setting DATA MODE START DATA PARITY STOP RTU 1 8 1 1 1 8 None 2 ASCII 1 7 1 1 1 7 None 2 FRONT DIP SW Node Address ADD...

Page 3: ...ECTOR DA DB DG SLD FG To Other Modbus Devices Note The FG terminal is not connected with the FG of the power supply module model R5 PS WIRING INSTRUCTIONS EURO TYPE CONNECTOR TERMINAL Modbus Applicabl...

Page 4: ...within the slave 17 Report Slave ID Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Reference 21 Write General Reference 22 Mask Write 4X Register 23 Read Write 4X Register...

Page 5: ...T 4 Module 4 Ai 1 INT 16 Module 16 Ai 1 INT 17 18 Module 1 Ai 1 Float 19 20 Module 2 Ai 1 Float 21 22 Module 3 Ai 1 Float 23 24 Module 4 Ai 1 Float 47 48 Module 16 Ai 1 Float Holding Registers 4X 1 Mo...

Page 6: ...hen there is an error in one or more channels the bit corresponding to the channels turns to 1 The bit corresponding to unmounted channels turns to 1 DC current output modules check output wire breakd...

Page 7: ...eger section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Negative values are represented in 2 s complements 0 15 4 POINT DISCRETE DATA models R5 DA4 DC4...

Reviews: