background image

DATA ALLOCATION MODE

The DIP SW located at the side of the module switches the unit’s data allocation mode.
The Data Allocation Mode 1 is used when all analog I/O modules are single-channel types.  In this mode, one (1) word is as-
signed for one I/O module.  The second channel on the dual-channel modules cannot be used.
The Data Allocation Mode 2 is used when one or more analog I/O modules are dual-channel types.  In this mode, two (2) words 
are assigned for one I/O module regardless of whether the second word area is required or not.
For discrete I/O, 16-channel area is automatically assigned to each module.  For example, with a 4-channel module, the bits 
assigned to ch. 5 through 16 remain “0.”

MODBUS I/O ASSIGNEMNTS

Coil (0X)

  1 –  16

Module   1

Do 1 – 16

  17 –   32

Module   2

Do 1 – 16

  33 –   48

Module   3

Do 1 – 16

  49 –   64

Module   4

Do 1 – 16

:

:

:

241 – 256

Module 16

Do 1 – 16

Inputs (1X)

  1 –  16

Module   1

Di 1 – 16

  17 –   32

Module   2

Di 1 – 16

  33 –   48

Module   3

Di 1 – 16

  49 –   64

Module   4

Di 1 – 16

:

:

:

241 – 256

Module 16

Di 1 – 16

257 – 272

Active Module Map

273 – 288

Status

289 – 320

Channel Status

 

Data Allocation Mode 1

Input Registers 
(3X)

1

Module 1

Ai 1 (INT)

2

Module 2

Ai 1 (INT)

3

Module 3

Ai 1 (INT)

4

Module 4

Ai 1 (INT)

:

:

:

16

Module 16

Ai 1 (INT)

17, 18

Module 1

Ai 1 (Float)

19, 20

Module 2

Ai 1 (Float)

21, 22

Module 3

Ai 1 (Float)

23, 24

Module 4

Ai 1 (Float)

:

:

:

47, 48

Module 16

Ai 1 (Float)

Holding Registers 
(4X)

1

Module 1

Ao 1 (INT)

2

Module 2

Ao 1 (INT)

3

Module 3

Ao 1 (INT)

4

Module 4

Ao 1 (INT)

:

:

:

16

Module 16

Ao 1 (INT)

17, 18

Module 1

Ao 1 (Float)

19, 20

Module 2

Ao 1 (Float)

21, 22

Module 3

Ao 1 (Float)

23, 24

Module 4

Ao 1 (Float)

:

:

:

47, 48

Module 16

Ao 1 (Float)

 

Data Allocation Mode 2

Input Registers 
(3X)

1

Module 1

Ai 1 (INT)

2

Module 1

Ai 2 (INT)

3

Module 2

Ai 1 (INT)

4

Module 2

Ai 2 (INT)

:

:

:

31

Module 16

Ai 1 (INT)

32

Module 16

Ai 2 (INT)

33, 34

Module 1

Ai 1 (Float)

35, 36

Module 1

Ai 2 (Float)

37, 38

Module 2

Ai 1 (Float)

39, 40

Module 2

Ai 2 (Float)

:

:

:

93, 94

Module 16

Ai 1 (Float)

95, 96

Module 16

Ai 2 (Float)

Holding Registers 
(4X)

1

Module 1

Ao 1 (INT)

2

Module 1

Ao 2 (INT)

3

Module 2

Ao 1 (INT)

4

Module 2

Ao 2 (INT)

:

:

:

31

Module 16

Ao 1 (INT)

32

Module 16

Ao 2 (INT)

33, 34

Module 1

Ao 1 (Float)

35, 36

Module 1

Ao 2 (Float)

37, 38

Module 2

Ao 1 (Float)

39, 40

Module 2

Ao 2 (Float)

:

:

:

93, 94

Module 16

Ao 1 (Float)

95, 96

Module 16

Ao 2 (Float)

Note: DO NOT access addresses other than mentioned above.  Such access may cause problems such as inadequate operation.

R5-NM1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-6104  Rev.8  P. 5 / 7

Summary of Contents for R5-NM1

Page 1: ...nit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 30 to 90 RH i...

Page 2: ...MODE RTU Binary ASCII 8 OFF ON 1 Bit assignment according to Parity and Data Mode setting DATA MODE START DATA PARITY STOP RTU 1 8 1 1 1 8 None 2 ASCII 1 7 1 1 1 7 None 2 FRONT DIP SW Node Address ADD...

Page 3: ...ECTOR DA DB DG SLD FG To Other Modbus Devices Note The FG terminal is not connected with the FG of the power supply module model R5 PS WIRING INSTRUCTIONS EURO TYPE CONNECTOR TERMINAL Modbus Applicabl...

Page 4: ...within the slave 17 Report Slave ID Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Reference 21 Write General Reference 22 Mask Write 4X Register 23 Read Write 4X Register...

Page 5: ...T 4 Module 4 Ai 1 INT 16 Module 16 Ai 1 INT 17 18 Module 1 Ai 1 Float 19 20 Module 2 Ai 1 Float 21 22 Module 3 Ai 1 Float 23 24 Module 4 Ai 1 Float 47 48 Module 16 Ai 1 Float Holding Registers 4X 1 Mo...

Page 6: ...hen there is an error in one or more channels the bit corresponding to the channels turns to 1 The bit corresponding to unmounted channels turns to 1 DC current output modules check output wire breakd...

Page 7: ...eger section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Negative values are represented in 2 s complements 0 15 4 POINT DISCRETE DATA models R5 DA4 DC4...

Reviews: