background image

R3S-YV4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8940  Rev.1  P. 4 / 4

WIRING INSTRUCTIONS

 

APPLICABLE WIRE SIZE

• 

Solid

: 0.2 to 1.0 mm

2

 (0.55 to 1.12 dia.)

• 

Stranded

: 0.2 to 1.5 mm

2

 

(Tinning wire ends may cause contact failure and therefore 
is not recommended.)

• Ferruled:

  Unsheathed: 0.25 to 1.5 mm

2

  Sheathed: 0.25 to 0.75 mm

2

• Expose wire conductors by 10 mm (0.39”).

Stripped length

10mm

 

CONNECTION PROCEDURE

Insert the wire end until it comes to a full stop while push-
ing slot with the tip of a screw driver as shown below.  Be 
sure wire insulation is not inside the terminal.

Screw Driver

Power wire

OUTPUT PIN ASSIGNMENT

PIN No.

FUNCTION

1

VH1

2

COM1

3

VL1

4

SLD

5

VH2

6

COM2

7

VL2

8

SLD

9

NC

10

NC

11

VH3

12

COM3

13

VL3

14

SLD

15

VH4

16

COM4

17

VL4

18

SLD

19

SLD

20

SLD

FUNCTIONS

 

OUTPUT HOLD or OUTPUT OFF

In normal conditions, the module outputs the signal from 
the preferred bus A.
When an error is detected, the output is switched to the 
data from the bus B.

• Output Hold

If both are in error, the module holds the signal and stands 
by until one of the communications recovers.

• Output OFF

If both are in error, the module outputs -15 % (or approx. 
-11.5 V) and stands by until one of the communications re-
covers. 

At the startup, it outputs -15 % (or approx. -11.5 V) until the 
communication is established and normal data is received.

Summary of Contents for R3S-YV4

Page 1: ...e highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous...

Page 2: ...put Range SW1 SW2 OUTPUT 1 SW1 OUTPUT 2 SW1 RANGE OUTPUT 3 SW2 OUTPUT 4 SW2 1 2 3 4 5 6 7 8 OFF OFF OFF OFF OFF OFF OFF OFF 10 10V DC ON OFF OFF OFF ON OFF OFF OFF 5 5V DC OFF ON OFF OFF OFF ON OFF OFF 1 1V DC ON ON OFF OFF ON ON OFF OFF 0 10V DC OFF OFF ON OFF OFF OFF ON OFF 0 5V DC ON OFF ON OFF ON OFF ON OFF 1 5V DC OFF ON ON OFF OFF ON ON OFF 0 1V DC Output Hold SW3 1 SW OUTPUT HOLD HOLD OFF S...

Page 3: ...NTERNAL BUS B 1 For dual redundant communication 2 To use shield line connect it to SLD terminal and ground the terminal 20 Note Do not connect wide span and narrow span simultaneously within the same channel Do not use void terminals 1 INTERNAL POWER WIDE SPAN NARROW SPAN OUTPUT 1 3 2 5 WIDE SPAN NARROW SPAN OUTPUT 2 7 6 11 WIDE SPAN NARROW SPAN OUTPUT 3 13 12 15 WIDE SPAN NARROW SPAN OUTPUT 4 17...

Page 4: ...Be sure wire insulation is not inside the terminal Screw Driver Power wire OUTPUT PIN ASSIGNMENT PIN No FUNCTION 1 VH1 2 COM1 3 VL1 4 SLD 5 VH2 6 COM2 7 VL2 8 SLD 9 NC 10 NC 11 VH3 12 COM3 13 VL3 14 SLD 15 VH4 16 COM4 17 VL4 18 SLD 19 SLD 20 SLD FUNCTIONS OUTPUT HOLD or OUTPUT OFF In normal conditions the module outputs the signal from the preferred bus A When an error is detected the output is sw...

Reviews: