COMPONENT IDENTIFICATION

1

20

ON

8

7

6

5

4

3

2

1

SW1

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

■ 

FRONT VIEW

■ 

SIDE VIEW

ERR LED

RUN LED

Output

Hold

Output 2 (SW1)

  or

Output 4 (SW2)

Range

Output 1 (SW1)

  or

Output 3 (SW2)

Functions

 

STATUS INDICATOR LED

RUN indicator:

 Bi-color (red/green) LED; 

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator:

  Green LED turns on in normal operating 

conditions.

 

SIDE DIP SW

(*) Factory setting

• Output Range: SW1, SW2

OUTPUT 1 (SW1)

OUTPUT 2 (SW1)

RANGE

OUTPUT 3 (SW2)

OUTPUT 4 (SW2)

1

2

3

4

5

6

7

8

OFF OFF OFF OFF OFF OFF OFF OFF -10 – +10V DC (*)
ON OFF OFF OFF ON OFF OFF OFF -5 – +5V DC
OFF ON OFF OFF OFF ON OFF OFF 1 – +1V DC
ON ON OFF OFF ON ON OFF OFF 0 – 10V DC
OFF OFF ON OFF OFF OFF ON OFF 0 – 5V DC
ON OFF ON OFF ON OFF ON OFF 1 – 5V DC
OFF ON ON OFF OFF ON ON OFF 0 – 1V DC

• Output Hold: SW3-1

SW

OUTPUT HOLD

HOLD (

*

)

OFF

SW3-1

OFF

ON

Note: Be sure to set unused SW3-2 through 3-4 to OFF.

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Zero Scale

-32000 to +32000

0

Full Scale

-32000 to +32000

10000

Zero Adjust

-320.00 to +320.00

0.00

Full Adjust

-32000 to +32000

1.0000

Unused

0: Enable
1: Disable

0: Enable

Summary of Contents for R3S-YV4

Page 1: ...e highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous...

Page 2: ...put Range SW1 SW2 OUTPUT 1 SW1 OUTPUT 2 SW1 RANGE OUTPUT 3 SW2 OUTPUT 4 SW2 1 2 3 4 5 6 7 8 OFF OFF OFF OFF OFF OFF OFF OFF 10 10V DC ON OFF OFF OFF ON OFF OFF OFF 5 5V DC OFF ON OFF OFF OFF ON OFF OFF 1 1V DC ON ON OFF OFF ON ON OFF OFF 0 10V DC OFF OFF ON OFF OFF OFF ON OFF 0 5V DC ON OFF ON OFF ON OFF ON OFF 1 5V DC OFF ON ON OFF OFF ON ON OFF 0 1V DC Output Hold SW3 1 SW OUTPUT HOLD HOLD OFF S...

Page 3: ...NTERNAL BUS B 1 For dual redundant communication 2 To use shield line connect it to SLD terminal and ground the terminal 20 Note Do not connect wide span and narrow span simultaneously within the same channel Do not use void terminals 1 INTERNAL POWER WIDE SPAN NARROW SPAN OUTPUT 1 3 2 5 WIDE SPAN NARROW SPAN OUTPUT 2 7 6 11 WIDE SPAN NARROW SPAN OUTPUT 3 13 12 15 WIDE SPAN NARROW SPAN OUTPUT 4 17...

Page 4: ...Be sure wire insulation is not inside the terminal Screw Driver Power wire OUTPUT PIN ASSIGNMENT PIN No FUNCTION 1 VH1 2 COM1 3 VL1 4 SLD 5 VH2 6 COM2 7 VL2 8 SLD 9 NC 10 NC 11 VH3 12 COM3 13 VL3 14 SLD 15 VH4 16 COM4 17 VL4 18 SLD 19 SLD 20 SLD FUNCTIONS OUTPUT HOLD or OUTPUT OFF In normal conditions the module outputs the signal from the preferred bus A When an error is detected the output is sw...

Reviews: