WIRING INSTRUCTIONS

 

TIGHTENING TORQUE

Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m

 

SOLDERLESS TERMINAL  unit: mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  
Applicable wire size: 0.25 to 0.75 mm

2

Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.

3.2 (.13) dia.

12 (.47) max.

6 max

.

(.24)

3 (.12) max.

 

HOW TO REMOVE SEPARABLE SCREW TERMINAL

The terminal block is separable in two pieces.  Evenly loos-
en two screws on top and bottom of the terminal block to 
separate.

FUNCTIONS

 

OUTPUT AT THE LOSS OF COMMUNICATION

• Output Hold

If the network module is in error, the module holds the sig-
nal at error and stands by until the communication recov-
ers.

• Output set value

If the network module is in error, the module holds the 
signal at error or power up and stands by until the com-
munication recovers. The the signal at error or power up is 
selectable with PC configurator software (Model: R30CFG)
Not depending on output at the loss of communication set-
ting, when power up the module holds the signal at error or 
power up and stands by until the normal data is received.

• Output wire breakdown detection

In the case of wire breakdown, output error is detected.  
Then, the ERR LED blinks in red and the flag of error is set 
on the PLC etc.

CONFIGURATOR SOFTWARE SETTING

The following parameter items can be set with using PC 
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.

 

CHANNEL INDIVIDUAL SETTING

ITEM

SETTING RANGE

DEFAULT
SETTING

Unused setting

CH enabled 
CH disabled

CH enabled

Fine zero adjust-
ment

-320.00 – +320.00 
(%)

0.00 (%)

Fine gain adjust-
ment

-3.2000 – +3.2000

1.0000

Scaled range zero

-32 000 – +32 000

0

Scaled range span

-32 000 – +32 000

10 000

Output range at 
Communication  
Failure or Power up

-15.00 – +115.00 (%) -15.00 (%)

 

CHANNEL BATCH SETTING

ITEM

SETTING RANGE

DEFAULT 
SETTING

Simulate Output

Normal output 
Simulation data

Normal output

Output at the loss 
of communication

Hold the output data 
User set data output

Hold the out-
put data