R30NE1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9019  Rev.1  P. 8 / 10

4) I/O Data (discrete input, discrete output, analog input, analog output) Assignment
  This unit recognizes type (No. of data areas) of each I/O module mounted on the same base, and automatically assigns it to 

each data area in the order of slot number.  See table below.

  Each data area is allocated only with the data of the assigned module and still has space.
  When data of each data area is transmitted to the host PC/PLC in the order of slot number, other types of data of the latter 

slot number, if any, are allocated and transmitted together so that each type of data is transmitted sequentially; that is, no 

blank data is transmitted. See figures below. 

  I/O Data Assignment is performed only when the power is turned on.
  Be sure to turn the power off and on again when the module configuration has been changed.
  The max. number of data areas per node is 64.
  Thus, the total number of data areas of the mounted I/O modules must be equal to or less than 64.
  When there is a blank slot, data of the latter slot number is transmitted to the host PC/PLC so that no blank data is trans-

mitted.

  The table below shows an example of I/O configuration and the figures show how I/O data are assigned.

BASE

SLOT NO.

MEDEL

DATA AREAS

R30BS08

PWR

R30PS1

COM

R30NE1

1

R30SV4

4

2

R30US2

2

3

R30TS4

4

4

R30YV4

4

5

R30XN16A

1

6

R30XN16A

1

7

R30YN16A

1

8

R30YN16A

1

R30EBS04

1

R3-SV8

8

2

R3-YV8

8

3

R3-DA32A

2

4

R3-DC32A

2

0

15

1

Slot No.7

2

4

3

■ 

Coil (0X)

The figure below indicates discrete output.

R30YN16A

R30BS08

Slot No.8

R30YN16A

Slot No.4

R3-DC32A

Do 16 points
Do 16 points
Do 16 points
Do 16 points

R30EBS04

0

15

1

Slot No.5

2

4

3

 Input (1X)

The figure below indicates discrete input.

R30XN16A

R30BS08

Slot No.6

R30XN16A

Slot No.3

R3-DA32A

Di 16 points
Di 16 points
Di 16 points
Di 16 points

R30EBS04

0

15

1

Slot No.1

2

4

3

5
6

8

7

9

11

10

12
13

15

14

16

18

17

■ 

Input Register (3X)

The figure below indicates analog input.

R30SV4

R30BS08

CH1

Slot No.2

R30US2

CH1

Slot No.3

R30TS4

CH1

CH2
CH3

Slot No.1

R3-SV8

CH1

CH4

CH2

CH2
CH3

CH8

CH2
CH3
CH4
CH5
CH6
CH7

CH9

R30EBS04

0

15

1

Slot No.4

2

4

3

5
6

8

7

9

11

10

12

 Holding Register (4X)

The figure below indicates analog output.

R30YV4

R30BS08

R30EBS04

CH1

Slot No.2

R3-YV8

CH1

CH3

CH2
CH3

CH6

CH4

CH2

CH4
CH5

CH7
CH8

Summary of Contents for R30NE1

Page 1: ...panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity HOT SWAPPABLE MODULES It is possible t...

Page 2: ...IEW BOTTOM VIEW SIDE VIEW Specifications Lock Tab Base Fixing Screw Positioning Guide STATUS INDICATOR LED ID FUNCTION COLOR STATUS PWR Main Unit Internal Power Green OFF Error Power off ON Normal RUN...

Page 3: ...age the positioning guide of the module with the In stallation Base 2 Pivot the module on the positioning guide and press it down until the lock tab clicks into place Positioning guide 3 Tighten the b...

Page 4: ...TCP Ethernet INTERNAL POWER PC CONFIGURATOR SETTING The following parameter items can be set with using PC Configurator Software model R30CFG Refer to the users manual for the R30CFG for detailed oper...

Page 5: ...n Windows OS C WINDOWS ping Enter IP address in decimal If the R30NE1 is successfully connected you will receive a response as follows ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 R...

Page 6: ...m Event Log X A status word an event counter a message count and a field of event bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 P...

Page 7: ...ction of the unit 1 Module Status indicates whether or not an I O module is mounted on each slot The bit corresponding to the mounted slot turns to 1 and the unmounted slot to 0 2 Error Status indicat...

Page 8: ...4 When there is a blank slot data of the latter slot number is transmitted to the host PC PLC so that no blank data is trans mitted The table below shows an example of I O configuration and the figure...

Page 9: ...it binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data...

Page 10: ...0 ANALOG DATA 32 bit data models R3 BA32A BC32A etc 32 bit binary data is used for BCD Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 0 15 0 Lower 16 bits 0...