background image

R30NE1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9019  Rev.1  P. 7 / 10

MODBUS I/O ASSIGNMENT

ADDRESS

DATA TYPE

DATA

Coil (0X)

1 to 2048

Discrete Output

Input (1X)

1 to 2048

Discrete Input

2049 to 2064

Module Status (R30 series)

2065 to 2080

Module Status (R3 series)

2081 to 2096

Error Status (R30 series)

2097 to 2112

Error Status (R3 series)

2113 to 2128

Data Error Status (R30 series)

2129 to 2144

Data Error Status (R3 series)

Input  Register (3X)

1 to 512

I

Analog Input

Holding  Register (4X)

1 to 512

I

Analog Output

 

DATA TYPE

I: Integer; 0 to 10000 (0 to 100%)
Note:  DO NOT access addresses other than mentioned above.  

Accessing such an address may result in problem such as malfunction of the unit.

1) Module Status indicates whether or not an I/O module is mounted on each slot. 
  The bit corresponding to the mounted slot turns to ‘1’, and the unmounted slot to ‘0’.

2) Error Status indicates occurrence of an error of each module as described below. 
  The bit corresponding to the module having an error turns to ‘1’.
  - R3-TSx, R3x-RSx, R3-US4 (input type: T/C or RTD): Input burnout
  - R3x-DA16A: Power input error or disconnection
  - R3x-YS4: Output disconnection
  - R3-PC16A: External power supply in error or disconnected

3) Data Error Status indicates occurrence of an error of each module as described below.
  The bit corresponding to the module having an error turns to ‘1’.
  - Analog input modules transmitting 0 to 100% scaling value: Input overrange (≤ -15% or ≥ 115%)
  - R30YS4: Output disconnection
  - R30TS4, R30RS4, R30USx (input type: T/C or RTD): Input burnout
  - R3-TSx, R3x-RSx, R3-US4 (input type: T/C or RTD): Input burnout
  - R3-US4 (input type: voltage): Input overrange (≤ -10% or ≥ 110%)

Summary of Contents for R30NE1

Page 1: ...panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity HOT SWAPPABLE MODULES It is possible t...

Page 2: ...IEW BOTTOM VIEW SIDE VIEW Specifications Lock Tab Base Fixing Screw Positioning Guide STATUS INDICATOR LED ID FUNCTION COLOR STATUS PWR Main Unit Internal Power Green OFF Error Power off ON Normal RUN...

Page 3: ...age the positioning guide of the module with the In stallation Base 2 Pivot the module on the positioning guide and press it down until the lock tab clicks into place Positioning guide 3 Tighten the b...

Page 4: ...TCP Ethernet INTERNAL POWER PC CONFIGURATOR SETTING The following parameter items can be set with using PC Configurator Software model R30CFG Refer to the users manual for the R30CFG for detailed oper...

Page 5: ...n Windows OS C WINDOWS ping Enter IP address in decimal If the R30NE1 is successfully connected you will receive a response as follows ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 R...

Page 6: ...m Event Log X A status word an event counter a message count and a field of event bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 P...

Page 7: ...ction of the unit 1 Module Status indicates whether or not an I O module is mounted on each slot The bit corresponding to the mounted slot turns to 1 and the unmounted slot to 0 2 Error Status indicat...

Page 8: ...4 When there is a blank slot data of the latter slot number is transmitted to the host PC PLC so that no blank data is trans mitted The table below shows an example of I O configuration and the figure...

Page 9: ...it binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data...

Page 10: ...0 ANALOG DATA 32 bit data models R3 BA32A BC32A etc 32 bit binary data is used for BCD Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 0 15 0 Lower 16 bits 0...

Reviews: