background image

R3-NM4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8331  Rev.4  P. 3 / 8

 

SIDE DIP SW

(*) Factory setting

• Data Allocation: SW1, SW2

Data Allocation Type*

2

 must be assigned to each I/O module 

slot position to specify how many data areas (four types) are 
to be occupied by each.
Two bits from SW1 and SW2 are assigned to each position, 
and data areas can be specified from the slot No. 1 through 
8.  Setting for No. 9 and later slots is identical to No. 8.

SW ASSIGNMENT

SLOT

SW1-1

SW1-2

1

SW1-3

SW1-4

2

SW1-5

SW1-6

3

SW1-7

SW1-8

4

SW2-1

SW2-2

5

SW2-3

SW2-4

6

SW2-5

SW2-6

7

SW2-7

SW2-8

8

SW SETTING

DATA ALLOCATION

OFF

OFF

1

ON

OFF

4

OFF

ON

8

ON

ON

16

*2.  Refer to the specifications of the related series for the Data 

Allocation Type of I/O modules.

• Dual Communication: SW3-1

When two network modules are mounted, one must be 
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work.  For single communication, the network module must 
always be set to ‘Main’ (OFF).

SW

DUAL COMMUNICATION

MAIN 

(*)

SUB

SW3-1

OFF

ON

• Input Error Data: SW3-2

Hold

: When the communication from an input module is lost 

due to the input module error, the network module holds the 
signal and stands by until the communication recovers.

Set to ‘0’

: When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD 

(*)

SET  ‘0’

SW3-2

OFF

ON

• Main/Sub Switching Control: SW3-3

The host PC or PLC can choose whether ‘Main’ or ‘Sub’ bus 
is used when the switching control is set to ‘Host.’
In ‘Normal’ mode, ‘Main’ bus is normally used, while ‘Sub’ 
bus is when the main communication has failed.
Be sure to match this control mode for both network mod-
ules in dual communication mode.

SW

MAIN/SUB SWITCHING CONTROL

NORMAL 

(*)

HOST

SW3-3

OFF

ON

Note: Set SW3-3 to OFF for use in single communication mode.

• LED Function: SW3-4

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED FUNCTION

RUN

ERR

OFF (*) Green when normal

Green when abnormal

ON

Red when receiving

Red when transmitting

PC CONFIGURATOR

The following parameter items can be set with PC Configurator Software (model: R3CON).
Refer to the users manual for the R3CON for detailed operation of the software program.

 

NETWORK MODULE SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

Time (no communication time)

0.2 – 3200.0 (sec.)

3.0 (sec.) 

Summary of Contents for R3-NM4

Page 1: ...tall the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperatu...

Page 2: ...le s node address in hexadecimal with SA1 and SA2 Setpoint adjustment 01 F7 FRONT DIP SW Factory setting Baud Rate SW6 1 6 2 6 3 6 4 SW BAUD RATE bps 115 2 k 57 6 k 38 4 k 28 8 k 19 2 k 14 4 k 9600 48...

Page 3: ...W3 2 Hold When the communication from an input module is lost due to the input module error the network module holds the signal and stands by until the communication recovers Set to 0 When the communi...

Page 4: ...conductor terminal 1 4 2 3 6 RUN RUN RUN CONTACT OUTPUT U V POWER INPUT WIRING INSTRUCTIONS M3 SCREW TERMINAL power input RUN contact output Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing be...

Page 5: ...13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave typ...

Page 6: ...error or disconnected Data Error Status indicates overrange R3 US4 out of 10 to 110 the other types out of 15 to 115 status for each module The bit corresponding to such module turns to 1 Main Sub Swi...

Page 7: ...ent 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature...

Page 8: ...trol 1 2 3 4 5 1 When the main sub switching control for both main and sub network is set to 0 all contact outputs are off and analog output modules output 15 2 When the main s setting is switched to...